ESIE15-13C
3.1.2 Service Setting
Unit No.
Second
Code No.
First
Code No.
1, 2, 6
1. Enter the field setting mode.
2. Enter the maintenance mode.
3. Select the mode No.
4. Select the unit No.
5. Carry out the necessary settings for each mode. (Mode 43 only possible for wireless remote
6. Return to the normal operation mode.
Mode
No.
Remote Controller
Unit NO.
SETTING
3
3
4
4
TEST
5
3
5
Press the inspection / test operation button for 4 seconds or more.
After having entered the field setting mode, press the inspection / test operation button for a
minimum of 4 seconds.
Set the desired mode No. with the up/down temperature setting button.
Select the indoor unit No. set with the time mode START/STOP button.
controller)
•
In case of Mode 43
Press timer ON / OFF button to decide the forced Fan ON.
•
In case of Mode 44
Set "Fan speed" with fan speed control button and "Air flow direction" with air flow
direction adjusting button, then press timer ON / OFF button to decide.
•
In case of Mode 45
Select the changed unit No. with
decide.
Press the inspection / test operation button 1 time.
Function
Content and Operation Method Example of Remote Controller Display
Forced Fan ON Turns the fan ON for each unit
individually.
43
Individual
Sets fan speed and air flow
Setting
direction for each unit
individually when using group
control.
44
Settings are made using the
"air flow direction adjust" and
"fan speed adjust" buttons.
Unit No.
Changes unit No.
Change
Set the unit No. after changing
with the programming time up-
down button.
45
Mode No.
Field
Setting
Mode
or
button, then press timer ON / OFF button to
Service Mode
Mode No.
Field Setting Mode
5
5
Second Code No.
First Code No.
3
1,2,6
1:
Fan
Low
speed
3:
High
0:Upper
Airflow direction
4:Lowest
Field setting No.
No. after change
21