Atex - Emerson Fisher 3610J Instruction Manual

And electro-pneumatic converter
Hide thumbs Also See for Fisher 3610J:
Table of Contents

Advertisement

Instruction Manual
D200149X012

ATEX

Standards Used for Certification
EN 60079-0: 2012
EN 60079-1: 2007
EN 60079-11: 2012
EN 60079-15: 2010
Special Conditions of Use
Intrinsically Safe
This equipment is intrinsically safe and can be used in potentially explosive atmospheres.
The electrical parameters of certified equipment which can be connected to the device must not exceed the following
values:
≤ 30 VDC
U
0
≤ 150 mA
I
0
≤ 1.25 W
P
0
Ambient temperature:
T6, at Tamb = 47_C
T5, at Tamb = 62_C
T4, at Tamb = 82_C
Flameproof
The flame path is other than required by EN 60079‐1. Contact the manufacturer for information on the dimensions of
the flameproof joints.
Electrical connections are typically made using either cable or conduit.
D If using a cable connection, the cable entry device shall be certified in type of explosion protection flameproof
enclosure "d", suitable for the conditions of use and correctly installed.
For ambient temperatures over 70_C, cables and cable glands suitable for at least 90_C shall be used.
D If using a rigid conduit connection, an Ex d certified sealing device such as a conduit seal with setting compound
shall be provided immediately to the entrance of the enclosure.
For ambient temperatures over 70_C, the wiring and setting compound in the conduit seal shall be suitable for at least
90_C.
Type n
No special conditions for safe use.
Refer to table 6 for additional approval information.
EN 60079-31: 2009
EN 61241-0: 2006
EN 61241-1: 2004
EN 61241-11: 2006
3610J and 3620J Positioners