Atex Intrinsic Safety; Atex Type N; Saa Intrinsic Safety, Type N - Emerson Fisher 3660 Instruction Manual

Table of Contents

Advertisement

3660 and 3661 Positioners
CERTIFICATE
CERTIFICATION OBTAINED
II 1 G —Intrinsic Safety
Gas
EEx ia IIC T4/T5/T6
ATEX
II 3 G
Gas
EEx nA IIC T6 —Type n
CERTIFICATION
Ex ia IIC —Intrinsic Safety
SAA
Ex n IIC —Type n

ATEX Intrinsic Safety

Type 3661
Special Conditions for Safe Use
This equipment is intrinsically safe and can be used
in potentially explosive atmospheres.
The electrical parameters of certified equipment
which can be connected to the device must not
exceed the following value:
U
 30 Vdc; I
 150 mA; P
0
0
Ambient Temperature:
T6, at T
= 47_C
amb
T5, at T
= 62_C
amb
T4, at T
= 71_C
amb
Refer to table 4 for additional approval information
and figure 30 for the ATEX approvals nameplate.

ATEX Type n

Type 3661
Special Conditions for Safe Use
The Type 3661 has an IP44 ingress protection: it is
only intended to be installed in an area where a
convenient protection is ensured against the entry of
solid foreign bodies and liquids which may decrease
the safety.
Refer to table 4 for additional approval information
and figure 30 for the ATEX approvals nameplate.
6
Table 4. Hazardous Area Classifications for Type 3661—ATEX
ENTITY RATING
U
= 30 Vdc
i
I
= 150 mA
i
P
= 1.25 W
i
C
= 0 nF
i
L
= 0 mH
i
Table 5. Hazardous Area Classifications for Type 3661—Australia (SAA)
CERTIFICATION OBTAINED
 1.25 W.
0
TEMPERATURE CODE
T4 (T
v 82°C)
amb
T5 (T
v 62°C)
amb
T6 (T
v 47°C)
amb
− − −
T6 (T
v 82°C)
amb
TEMPERATURE CODE
T4 (T
v 40°C)
amb
T4 (T
v 40°C)
amb

SAA Intrinsic Safety, Type n

Type 3661
Conditions of Certification
1. It is a condition of certification that the following
parameters are taken into consideration during
installation when the equipment is used as an Ex ia
apparatus:
Input Parameters
Maximum Input Voltage U
Maximum Input Current I
Maximum Internal Capacitance C
Maximum Internal Inductance L
2. It is a condition of safe use that the input voltage
does not exceed 32 Volts when the equipment is
used as an Ex n apparatus.
3. It is a condition of safe use that the equipment
shall be mounted such that the exhaust vents will be
self-draining.
4. It is a condition of safe use that the cable gland or
conduit adaptor with an ingress protection rating of
IP54 must be used in the conduit entry in order to
maintain the IP rating of the enclosure.
5. It is a condition of safe use that the irrelevant
explosion protection marking codes on the
certification label are permanently scribed off upon
completion of commissioning.
Refer to table 5 for additional approval information,
and figure 31 for the SAA approvals nameplate.
Instruction Manual
Form 5265
March 2006
ENCLOSURE RATING
IP44
IP44
ENCLOSURE RATING
IP54
IP54
2-Way terminal block
32 V
i
150 mA
i
0 µF
i
0 mH
i

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fisher 3661

Table of Contents