Article number
Input current
Current consumption, max.
Output voltage
Rated value (DC)
Power loss
Power loss, typ.
Address area
Address space per module
Outputs
•
Hardware configuration
Automatic encoding
Mechanical coding element
•
Selection of BaseUnit for connection variants
1-wire connection
•
2-wire connection
•
3-wire connection
•
4-wire connection
•
Digital outputs
Type of digital output
Number of digital outputs
Current-sourcing
Short-circuit protection
Response threshold, typ.
•
Limitation of inductive shutdown voltage to
Controlling a digital input
Switching capacity of the outputs
with resistive load, max.
•
on lamp load, max.
•
Load resistance range
lower limit
•
upper limit
•
Output current
for signal "1" rated value
•
for signal "1" permissible range, max.
•
for signal "0" residual current, max.
•
Output delay with resistive load
"0" to "1", max.
•
"1" to "0", max.
•
Digital output module DQ 8x24VDC/0.5A BA (6ES7132-6BF01-0AA0)
Manual, 09/2017, A5E36107249-AC
6ES7132-6BF01-0AA0
45 mA; without load
24 V
1 W
1 byte
Yes
Yes
BU type A0
BU type A0
BU type A0 with AUX terminals
BU type A0 + Potential isolation module
Source output (PNP, current-sourcing)
8
Yes
Yes; per channel, electronic
1 A
Typ. L+ (-50 V)
Yes
0.5 A
5 W
48 Ω
100 kΩ
0.5 A
0.5 A
10 µA
100 µs; at rated load
150 µs; at rated load
Technical specifications
6.1 Technical specifications