Interrupts/diagnostics alarms
5.1 Status and error display
Meaning of the LEDs
The following tables show the meaning of the status and error displays. Corrective measures
for diagnostics alarms can be found in section Diagnostics alarms (Page 23).
DIAG LED
Table 5- 1
DIAG LED
Channel status LED
Table 5- 2
Channel status
PWR LED
Table 5- 3
PWR LED
22
Error display of the DIAG LED
Meaning
Backplane bus supply of the ET 200SP not OK
Off

Module parameters not assigned
Flashes
Module parameters assigned and no module diagnostics
On
Module diagnostics is available
Flashes
Status display of the channel status LED
Meaning
LED
Channel deactivated or activated and process signal = 0
Off

Channel activated and process signal = 1
On
Status display of the PWR LED
Meaning
Missing supply voltage L+
Off

Supply voltage L+ present
On