10 Connecting to PLC of GE Fanuc Automation Inc.
10-5 Cable Fabrication
RS232 Communication for GE Fanuc Series SNP
Communicating with PT by directly using the communication cable provided by GE
RS232 Communication for VersaMax Series
D-Sub
9Pin
(Female)
RS232 Communication for VersaMax Micro & Nano Series
D-Sub
9Pin
(Female)
RS232 Communication Cable for Communication Module CMM311
D-Sub
9Pin
(Female)
10-8
PT (COM1/COM2)
Signal
Pin No.
SD
2
RD
3
SG
9
PT (COM1/COM2)
Signal
Pin No.
SD
2
RD
3
SG
9
PT (COM1/COM2)
Signal
Pin No.
SD
2
RD
3
SG
9
VersaMax series PLC
Pin No.
Signal
3
RD
2
TD
5
GND
VersaMax Micro&Nano series PLC
Pin No.
Signal
6
RX
5
TX
1
GND
CMM311 port1/port2 teminal
Pin No.
Signal
3
RXD
2
TXD
7
GND
4
RTS
5
CTS
8
DCD
20
DTR
NB-series Programmable Terminals Host Connection Manual (V108)
D-Sub
9Pin
(Female)
RJ45
terminal
D-Sub
25Pin
(Female)