Legend - Siemens VALVEGYR LDU11.323A17 User Manual

Valve proving system for automatic shutoff valves ldu11...
Table of Contents

Advertisement

Legend

20/21
Building Technologies Division
A, A1, A2
Gas valves controlled to evacuate the test space
AGK25
PTC resistor
AL
Alarm signal for «leaking valve»
ar...
Contacts (operating relay)
B
Gas valve controlled to fill the test space
C
Vent valve, normally open; closed during valve proving test from the be-
ginning of «Test1»
DW
Pressure switch for valve proving test (does not replace the gas pressure
switch used to signal lack of gas)
E
Safety shutoff valve, dead closed (optional)
EK
Lockout reset button (internal)
EK2
Remote lockout reset button
FSV
Flame signal amplifier
GP
Gas pressure switch (for lack of gas)
H
Main switch
ION
Ionization probe
K1...4
Internal relays
hr...
Contacts (auxiliary relay)
LP
Air pressure switch
M...
Fan («M2»: pre- and postpurging)
NT
Power supply
PL
Reference pressure for SKP7...
R
Control thermostat or pressurestat (e.g. boiler control thermostat)
RB
Pipe orifice; its diameter must be determined such that in the event of a
leaking ignition gas valve (A), the ignition flame cannot afterburn on com-
pletion of the second safety time so that presence of the main flame can-
not be simulated
SB
Safety limit thermostat
STB
Safety limit thermostat
T
Delay off time relay; the time should be set to approx. «t16» (min. «t7»...
max. «t10») of the burner control
W
Limit thermostat or pressure switch or pressure limiter
Z
Ignition transformer
t7
Interval between start command and power at terminal 7 (start delay for
«M2»)
t10
Interval from start to the beginning of the air pressure check, excluding
running time of air damper
t16
Interval until OPEN command for the air damper is given
CC1N7696en