Use
____________________________________________________________________________________________
Available models
Siemens Building Technologies SpA
®
INTELLIGAS
Gas leak detection system
for heating rooms and similar environments
Electronic control unit for gas leak detection with single sensor aimed to drive a
gas flow cut-off 12VDC normally closed (NC) or normally open (NO) solenoid
valve. Single threshold sensor with tin dioxide sensing element. Possible control
of auxiliary devices (hooters, flashing lights, fans...) or 230VAC solenoid valves
through built-in relay. 24VAC power supply. Built-in battery charger for optional
external 12V buffer battery charge with automatic intervention in case of power
failure.
LYC11 control unit is used, connected to a QA..13/A sensor, for optical/acoustic signaling
or to drive a gas flow cut-off valve in presence of dangerous concentrations of:
• methane (CH4)
• LPG
• carbon monoxide (CO)
note: Only one sensor QA..13/A can be connected to the control unit
Description
Control unit
Sensor for methane gas IP44
Sensor for LPG gas IP44
Sensor for carbon monoxide (CO) IP44
Gas solenoid valves 12V DC
Gas solenoid valves 230V AC
LYC11
Type
LYC11
QAG13/A
QAG13.P/A
QAO13/A
E..D (NC) or E..E (NO)
E..D-AC (NC) or E..E-AC (NO)
CE1N7601e 05-04-2004
7
601
1/8

Advertisement

loading

Summary of Contents for Siemens LYC11

  • Page 1 12V buffer battery charge with automatic intervention in case of power failure. ____________________________________________________________________________________________ LYC11 control unit is used, connected to a QA..13/A sensor, for optical/acoustic signaling or to drive a gas flow cut-off valve in presence of dangerous concentrations of: • methane (CH4) •...
  • Page 2 ___________________________________________________________________________________________ Mounting The LYC11 can be installed as follows: LYC11 Onto a DIN bar minimum length 120 mm Onto a wall using 2 screws On panel front end using a DIN bar minimum length 150mm and 2 hex spacers 50 mm, screws and washers.
  • Page 3 VALVE MODE mode selection position allows to set EV output constantly powered in case of VALVE / MODE CONT. PULSE gas alarm, while position allows to set it powered by impulses PULSE at 10s intervals. Siemens Building Technologies SpA CE1N7601e 05-04-2004...
  • Page 4: Operation

    1.8Kohm 1/2W (supplied with the equipment) in the EV terminal. This will avoid any wrong valve fault signal. ______________________________________________________________________________________________ After powering up (24V AC) the control unit LYC11 carries out these phases in sequence: Operation 1. Sensor preheating phase. During this phase, about 1min, the detection system is not operational.
  • Page 5: Environmental Compatibility And Disposal

    Shipping case The LYC11 shipping case can be recycled. Retain it for future use or in case of product return to the manufacturer. Siemens Building Technologies SpA...
  • Page 6: Technical Data

    Sensor IP44 for Methane detection (CH4) QAG13.P/A Sensor IP44 LPG detection QAO13/A Sensor IP44 for carbon monoxide (CO) detection _____________________________________________________________________________________________ Technical data Control unit LYC11 Power supply voltage 24VAC +/-10% Frequency 50 Hz Power consumption 21VA max (with battery under charge)
  • Page 7: Wiring Diagrams

    12V 4÷6 Ah (not supplied by Siemens) Buffer charge with automatic intervention current limit Wiring diagrams Diagram 1: Control unit LYC11 with sensor QA..13/A and 12V DC solenoid valve type E..D. 12V buffer battery. Optional control of signal lamps and air extractors. 230V AC 24V AC B A T T .
  • Page 8 ____________________________________________________________________ Diagram 2: Control unit LYC11 with sensor QA..13/A and 230V AC solenoid valve type E..D-AC. Optional control for signal lamp 230V AC 24V AC B A T T . NO NC Symbols: Options N1 = Control unit LYC11 L1 = 230VAC signal lamp B1 = Sensor QA..13/A...