Electrical Data For Indoor Models; Electrical Data - Evaporator Units - York R-410A Technical Manual

Split-system air-cooled condensing units and air handlers
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

505428-YTG-V-0417

Electrical Data For Indoor Models

Electrical Data - Evaporator Units

Motor HP
Power Supply
208-3-60
230-3-60
1.5
460-3-60
575-3-60
208-3-60
230-3-60
1.5
460-3-60
575-3-60
66
Supply
Blower
Electric Heat Option
Motor
FLA
Model
KW
NC090 C00B (CONSTANT VOLUME)
None
---
10 KW
7.5
5.0
16 KW
12
26 KW
19.5
36 KW
27
None
---
10 KW
10
5.2
16 KW
16
26 KW
26
36 KW
36
None
---
10 KW
10
2.6
16 KW
16
26 KW
26
36 KW
36
None
---
10 KW
10
2.0
16 KW
16
26 KW
26
36 KW
36
NL090 C00B (INTELLISPEED)
None
---
10 KW
7.5
4.3
16 KW
12
26 KW
19.5
36 KW
27
None
---
10 KW
10
4.2
16 KW
16
26 KW
26
36 KW
36
None
---
10 KW
10
2.1
16 KW
16
26 KW
26
36 KW
36
None
---
10 KW
10
1.8
16 KW
16
26 KW
26
36 KW
36
MCA
(Amps)
Stages
Amps
---
---
6.3
1
20.8
32.3
2
33.4
47.9
2
54.2
73.9
2
75.1
99.9
---
---
6.5
1
24.1
36.6
2
38.5
54.6
2
62.5
84.7
2
86.6
114.8
---
---
3.3
1
12
18.3
2
19.2
27.3
2
31.3
42.3
2
43.3
57.4
---
---
2.5
1
9.6
14.5
2
15.4
21.7
2
25
33.8
2
34.6
45.8
---
---
5.4
1
20.8
31.4
2
33.4
47.0
2
54.2
73.0
2
75.1
99.1
---
---
5.3
1
24.1
35.3
2
38.5
53.4
2
62.5
83.4
2
86.6
113.5
---
---
2.6
1
12.0
17.7
2
19.2
26.7
2
31.3
41.7
2
43.3
56.8
---
---
2.3
1
9.6
14.3
2
15.4
21.5
2
25.0
33.5
2
34.6
45.6
Johnson Controls Unitary Products
2
Max Fuse
/
1
3
Breaker
Size
(Amps)
15
35
50
80
100
15
40
60
90
125
15
20
30
45
60
15
15
25
35
50
15
35
50
80
100
15
40
60
90
125
15
20
30
45
60
15
15
25
35
50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents