Yd180/Nd180/Nm180 - York R-410A Technical Manual

Split-system air-cooled condensing units and air handlers
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

YD180/ND180/NM180

Air on
Evaporator Coil
Total
1
Capacity
WB
CFM
(MBh)
(°F)
77
218.6
72
205.5
3750
67
192.4
62
184.8
77
225.1
72
211.6
4500
67
198.1
62
190.3
57
172.5
77
231.7
72
217.8
5250
67
203.9
62
195.8
57
177.6
77
238.2
72
223.9
6000
67
209.6
62
201.3
57
182.6
72
228.7
67
214.1
6750
62
205.6
57
186.5
72
233.4
67
218.5
7500
62
209.8
57
190.4
77
208.0
72
193.3
3750
67
178.6
62
165.9
77
213.1
72
198.0
4500
67
183.0
62
169.9
57
172.2
77
218.2
72
202.8
5250
67
187.4
62
174.0
57
176.4
77
223.2
72
207.5
6000
67
191.7
62
178.0
57
180.5
72
211.1
67
195.0
6750
62
181.1
57
183.6
72
214.6
67
198.3
7500
62
184.1
57
186.7
Johnson Controls Unitary Products
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
75°F
12.6
99.2
83.3
67.4
12.1
124.0
108.1
92.2
76.2
11.7
148.8
132.9
117.0
101.0
11.4
184.8
160.1
142.1
126.2
12.7
109.7
91.8
73.9
12.2
136.9
119.0
101.1
83.3
11.8
164.1
146.2
128.4
110.5
11.5
190.3
173.8
155.9
138.1
11.3
172.5
172.5
158.3
140.4
12.8
120.1
100.3
80.5
12.3
149.7
129.9
110.1
90.3
11.9
179.4
159.6
139.8
120.0
11.6
195.8
187.6
169.8
150.0
11.4
177.6
177.6
172.3
152.5
12.8
130.5
108.7
87.0
12.4
162.5
140.8
119.1
97.3
11.9
194.6
172.9
151.2
129.4
11.6
201.3
201.3
183.6
161.9
11.5
182.6
182.6
182.6
164.6
12.5
173.9
149.9
125.9
101.9
12.1
206.6
183.7
159.8
135.8
11.8
205.6
205.6
196.7
172.7
11.6
186.5
186.5
186.5
164.4
12.7
185.2
158.9
132.7
106.4
12.2
218.5
194.6
168.4
142.1
11.9
209.8
209.8
209.8
183.6
11.8
190.4
190.4
190.4
164.1
95°F
15.0
93.5
76.5
59.6
14.7
119.9
102.9
85.9
68.9
14.5
146.3
129.3
112.3
95.3
14.3
165.9
159.4
134.7
117.7
15.0
102.4
83.7
64.9
14.7
131.2
112.4
93.7
74.9
14.5
160.0
141.2
122.4
103.7
14.3
169.9
165.6
146.8
128.1
14.4
172.2
170.4
151.6
132.9
15.0
111.4
90.8
70.3
14.8
142.5
121.9
101.4
80.9
14.5
173.6
153.1
132.5
112.0
14.3
174.0
171.8
158.9
138.4
14.4
176.4
175.4
164.2
143.6
15.0
120.3
98.0
75.6
14.8
153.8
131.5
109.1
86.8
14.5
187.3
165.0
142.6
120.3
14.3
178.0
178.0
171.1
148.7
14.4
180.5
180.5
176.7
154.3
14.8
167.0
142.1
117.1
92.1
14.6
192.8
178.0
153.0
128.1
14.4
181.1
181.1
177.6
152.6
14.5
183.6
183.6
181.7
156.7
14.9
180.2
152.6
125.0
97.4
14.6
198.3
191.0
163.4
135.8
14.4
184.1
184.1
184.1
156.5
14.5
186.7
186.7
186.7
159.1
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
75
70
65
-
-
-
213.3
-
-
199.4
85.1
-
185.5
110.2
94.3
175.3
-
-
-
219.1
-
-
204.8
92.6
-
190.6
120.2
102.3
180.1
122.5
104.7
172.4
-
-
-
224.9
-
-
210.3
100.2
-
195.6
130.2
110.4
184.9
132.7
112.9
177.0
-
-
-
230.7
-
-
215.7
107.7
-
200.7
140.1
118.4
189.7
142.9
121.2
181.5
-
-
219.9
111.8
-
204.5
148.7
124.8
193.3
140.4
116.4
185.0
-
-
224.0
115.9
-
208.4
157.3
131.1
197.0
137.9
111.6
188.5
-
-
-
199.1
-
-
184.5
78.3
-
169.8
100.7
83.7
159.3
-
-
-
203.6
-
-
188.6
84.9
-
173.7
109.3
90.5
162.9
114.1
95.3
165.1
-
-
-
208.1
-
-
192.8
91.4
-
177.5
117.9
97.3
166.5
123.1
102.5
168.7
-
-
-
212.6
-
-
197.0
98.0
-
181.3
126.4
104.1
170.1
132.0
109.7
172.4
-
-
201.2
103.1
-
185.2
127.7
102.7
173.7
131.7
106.8
176.1
-
-
205.4
108.2
-
189.1
128.9
101.3
177.4
131.5
103.9
179.8
505428-YTG-V-0417
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
85°F
13.8
96.4
79.9
63.5
13.4
122.0
105.5
89.1
72.6
13.1
147.6
131.1
114.6
98.2
12.8
175.3
159.7
138.4
121.9
13.8
106.1
87.7
69.4
13.5
134.0
115.7
97.4
79.1
13.1
162.0
143.7
125.4
107.1
12.9
180.1
169.7
151.4
133.1
12.9
172.4
172.4
155.0
136.6
13.9
115.7
95.5
75.4
13.5
146.1
125.9
105.8
85.6
13.2
176.5
156.3
136.1
116.0
12.9
184.9
179.7
164.4
144.2
12.9
177.0
177.0
168.2
148.1
13.9
125.4
103.3
81.3
13.6
158.2
136.1
114.1
92.1
13.2
191.0
168.9
146.9
124.9
13.0
189.7
189.7
177.3
155.3
13.0
181.5
181.5
181.5
159.5
13.7
170.4
146.0
121.5
97.0
13.3
199.7
180.9
156.4
131.9
13.1
193.3
193.3
187.2
162.7
13.1
185.0
185.0
185.0
160.5
13.8
182.7
155.8
128.9
101.9
13.4
208.4
192.8
165.9
139.0
13.2
197.0
197.0
197.0
170.1
13.2
188.5
188.5
188.5
161.6
105°F
16.8
88.3
74.5
57.6
16.6
117.4
100.5
83.5
66.5
16.4
146.6
126.4
109.4
92.4
16.3
159.3
156.1
131.5
114.6
16.8
101.0
81.8
62.7
16.6
129.2
110.1
90.9
71.7
16.4
157.5
138.3
119.1
100.0
16.3
162.9
160.7
143.2
124.1
16.3
165.1
164.2
145.2
126.0
16.8
113.8
89.2
67.8
16.6
141.0
119.7
98.3
77.0
16.4
168.3
150.2
128.9
107.5
16.3
166.5
165.4
154.9
133.6
16.4
168.7
168.3
157.0
135.6
16.8
126.5
96.5
72.9
16.6
152.8
129.3
105.7
82.2
16.4
179.1
162.1
138.6
115.0
16.3
170.1
170.1
166.6
143.1
16.4
172.4
172.4
168.8
145.3
16.6
166.0
140.0
114.0
88.0
16.4
184.1
173.8
149.4
123.4
16.3
173.7
173.7
172.0
146.0
16.4
176.1
176.1
174.3
148.3
16.6
179.1
150.7
122.2
93.8
16.4
189.1
185.5
160.2
131.7
16.3
177.4
177.4
177.4
149.0
16.3
179.8
179.8
179.8
151.4
75
70
65
-
-
-
-
-
81.7
-
105.5
89.0
-
-
-
-
-
88.8
-
114.7
96.4
118.3
100.0
-
-
-
-
-
95.8
-
124.0
103.8
127.9
107.7
-
-
-
-
-
102.8
-
133.3
111.2
137.5
115.4
-
-
107.4
-
138.2
113.7
136.1
111.6
-
-
112.1
-
143.1
116.2
134.7
107.8
-
-
-
-
-
75.5
-
97.6
80.6
-
-
-
-
-
80.8
-
104.9
85.7
106.8
87.7
-
-
-
-
-
86.1
-
112.2
90.9
114.3
92.9
-
-
-
-
-
91.5
-
119.5
96.0
121.8
98.2
-
-
97.4
-
120.0
94.0
122.4
96.4
-
-
103.3
-
120.5
92.1
122.9
94.5
29