Application Factors - Rated Cfm Vs. Actual Cfm; Electrical Data - Cooling Only (60 Hz) - York AVY24 THRU 60 Technical Manual

Single piece variable speed air handlers for use with split-system cooling & heat pumps
Table of Contents

Advertisement

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow
Capacity Factor
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
Blower - Diameter x Width
HP
Motor
Nominal RPM
Voltage
Amps
Full Load (230)
Type
1
Size
Filter
Permanent Type Kit
Shipping / Operating Weight (lbs.)
1.Field supplied.

ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Johnson Controls Unitary Products
80%
0.96
AVY24B**H21
10 x 7
1/3
1200
2.8
16 x 20 x1
1PF0601BK
140/134
Total Motor Amps
60 Hertz
208V
230V
3.2
2.8
4.7
4.3
6.1
5.0
6.1
5.0
7.8
7.0
7.8
7.0
90%
Rated CFM
0.98
1.00
AVY36C**H21
10 x 7
1/2
1200
4.3
DISPOSABLE OR PERMANENT
20 x 20 x1
1PF0602BK
170/164
Minimum Circuit Ampacity
60 Hertz
208V
230V
4.0
3.5
5.9
5.4
7.6
6.9
7.6
6.9
9.7
8.8
9.7
8.8
256819-YTG-J-1208
110%
1.02
AVY48D**H21
SVY48D**N21
10 x 10
3/4
1200
230
5.5
22 x 20 x1
1PF0603BK
AV - 196/185
SV - 194/181
Max. O.C.P.
1
Amps/Type
15
15
15
15
15
15
120%
1.03
AVY60D**H21
SVY60D**N21
10 x 10
1
1200
7.0
22 x 20 x1
1PF0603BK
AV - 199/188
SV - 195/184
Minimum Wire
Size A.W.G.
14
14
14
14
14
14
5

Advertisement