Motor Constants Functions - Hitachi SJ300 Series Manual

Sensorless vector contro
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Code
Name
Terminal (11) active state
C031
Terminal (12) active state
C032
Terminal (13) active state
C033
Terminal (14) active state
C034
Terminal (15) active state
C035
Alarm relay terminal active state
C036
Overload signal output mode
C040
Overload level setting
C041
Arrival frequency setting for acceleration
C042
Arrival frequency setting for deceleration
C043
PID deviation level setting
C044
Arrival frequency setting for acceleration(2)
C045
Arrival frequency setting for deceleration(2)
C046
Over-torque(Forward-driving) level setting
C055
Over-torque(Reverse-regenerating) level setting
C056
Over-torque(Reverse-driving) level setting
C057
Over-torque(Forward-regenerating) level setting
C058
Electronic thermal warning level setting
C061
Alarm code input
C062
Zero speed detection level
C063
Data command method
C070
Communication speed selection
C071
Node allocation
C072
Communication data length selection
C073
Communication parity selection
C074
Communication stop bit selection
C075
Communication wait time
C078
O input span calibration
C081
OI input span calibration
C082
O2 input span calibration
C083
Thermistor input tuning
C085
AM terminal offset tuning
C086
AMI terminal meter tuning
C087
AMI terminal offset tuning
C088
Debug mode enable
C091
UP/DOWN memory mode selection
C101
Reset mode selection
C102
Restart frequency after reset
C103
Overload level setting(2)
C111
O input zero calibration
C121
OI input zero calibration
C122
O2 input zero calibration
C123
●H GROUP: MOTOR CONSTANTS FUNCTIONS
Code
Name
H001
Auto-tuning setting
H002
Motor data selection for first motor
H202
Motor data selection for second motor
H003
Motor capacity
H203
Motor capacity for second motor
H004
Motor poles setting
H204
Motor poles setting for second motor
H005
Motor speed constant
H205
Motor speed constant for second motor
H006
Motor stabilization constant
H206
Motor stabilization constant for second motor
H306
Motor stabilization constant for third motor
H020
Motor constant R1 setting for first motor
H220
Motor constant R1 setting for second motor
H021
Motor constant R2 setting for first motor
H221
Motor constant R2 setting for second motor
H022
Motor constant L setting for first motor
H222
Motor constant L setting for second motor
Note:[ ]75kW and over
17
Description
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(During accel./decel) / 01(At constant speed)
0.00
rated current-2.00
rated current
×
×
0.00-99.99/ 100.0-400.0Hz
0.00-99.99/ 100.0-400.0Hz
0.0-100%
0.00-99.99/ 100.0-400.0Hz
0.00-99.99/ 100.0-400.0Hz
0.-200.%
[0.-180.%]
0.-200.%
[0.-180.%]
[0.-180.%]
0.-200.%
0.-200.%
[0.-180.%]
0.-100.%
00(Disabled) / 01(3-bit) / 02(4-bit)
0.00-99.99/100.0Hz
02(Operator) / 03(RS-485) / 04 (Expansion card 1) / 05(Expansion card 2)
02(Test) / 03(2400bps) / 04(4800bps) / 05(9600bps) / 06(19200bps)
1.-32.
7(7-bit) / 8(8-bit)
00(No parity) / 01(Even) / 02(Odd)
1(1-bit) / 2(2-bit)
0.-1000.msec.
0-6553(65,530)
0-6553(65,530)
0-6553(65,530)
0.0-1000.
0.0-10.0V
0.-255.%
0.-20.0mA
00(No display) / 01(Display)
00(Clear previous frequency) / 01(Keep previous frequency)
00(Cancel trip state when reset signal turns ON) / 01(Cancel
trip state when reset signal turns OFF) / 02(Cancel trip state
when reset signal turns ON(Enable during trip state))
00(Restart at 0Hz) / 01(Resume operation after frequency matching)
0.00
rated current-2.00
rated current
×
×
0.-9999./ 1000-6553(10,000-65,530)
0.-9999./ 1000-6553(10,000-65,530)
0.-9999./ 1000-6553(10,000-65,530)
Description
00(NOR:Disable) / 01(NOR:No rotation) / 02(AUT:Rotation)
00(Hitachi standard motor) / 01(Auto-data) / 02(Adaptive-data)
00(Hitachi standard motor) / 01(Auto-data) / 02(Adaptive-data)
0.20-75.0(kW)
[ 0.2-160 (kW) ]
0.20 - 75.0(kW)
[ 0.2-160 (kW)]
2/4/6/8
2/4/6/8
0.001 - 9.999/10.00 - 65.53
0.001 - 9.999/10.00 - 65.53
0. - 255.
0. - 255.
0. - 255.
0.000 - 9.999/10.00 - 65.53
0.000 - 9.999/10.00 - 65.53
0.000 - 9.999/10.00 - 65.53
0.000 - 9.999/10.00 - 65.53
0.00 - 9.99/100.00 - 655.3
0.00 - 9.99/100.00 - 655.3
[
= Allowed
= Not permitted
×
Default Setting
Run-time
Run-time Data Edit
Setting
(Enabled at b031)
-FE(CE) -FU(UL)
00
00
×
00
00
×
00
00
×
00
00
×
00
00
×
01
01
×
01
01
×
×
Rated current
Rated current
0.00
0.00
×
0.00
0.00
×
3.0
3.0
×
0.00
0.00
×
0.00
0.00
×
100.
100.
×
100.
100.
×
100.
100.
×
100.
100.
×
80.
80.
×
00
00
×
0.00
0.00
×
02
02
×
×
04
04
×
1.
1.
×
7
7
×
00
00
×
1
1
×
0.
0.
×
Factory set
Factory set
Factory set
Factory set
Factory set
Factory set
105.0
105.0
0.0
0.0
80.
80.
4.0
4.0
00
00
×
00
00
×
00
00
×
00
00
×
×
Rated current
Rated current
Factory set
Factory set
Factory set
Factory set
Factory set
Factory set
[
= Allowed
×
= Not permitted
Default Setting Run-time
Run-time Data Edit
Setting
(Enabled at b031)
-FE(CE) -FU(UL)
00
00
×
×
00
00
×
×
×
×
00
00
×
Factory set
Factory set
×
Factory set
Factory set
×
×
4
4
×
×
4
4
×
×
1.590
1.590
1.590
1.590
100.
100.
100.
100.
100.
100.
According
According
×
×
to capacity
to capacity
According
According
×
×
to capacity
to capacity
According
According
×
×
to capacity
to capacity
According
According
×
×
to capacity
to capacity
According
According
×
×
to capacity
to capacity
According
According
×
×
to capacity
to capacity
]
]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents