Descriptions of functions
10.2 PROFIBUS
Bit
Meaning
13
1 = Motorized
potentiometer, higher
14
1 = Motorized
potentiometer,
lower
Note:
If "Motorized potentiometer, higher" and "Motorized potentiometer, lower" both 0 or 1 at the same time, the
current setpoint is frozen.
15
1 = CDS bit 0
(only with telegrams p0922
= 20!)
Reserved
Setpoints
Speed setpoint A, 16-bit (NSET_A)
● Speed setpoint with 16-bit resolution incl. sign bit
● Bit 15 determines the setpoint sign:
● The speed setpoint is scaled via parameter p2000.
PCS7-specific setpoints (PCS7 x)
Depending on the configuration, KP adaptation values for the speed controller and
acceleration values or other setpoints, for example, are transferred here.
10.2.7

Description of status words and actual values

Overview
Table 10- 8
Overview of status words and actual values
Abbreviation
Description
ZSW1
Status word 1
NACT_A
Speed setpoint A (16-bit)
NACT_SMOOTH
Actual speed value, smoothed
IAACT_SMOOTH
Actual current value, smoothed
MACT_SMOOTH
Actual torque value, smoothed
PACT_SMOOTH
Actual power value, smoothed
316
Explanation
Only when p0922 = 1 or 352, otherwise reserved
Only when p0922 = 1 or 352, otherwise reserved
1: Command data set changeover (CDS) bit 0 is
active.
0: Command data set changeover (CDS) bit 0 is
inactive.
When p0922 = 1 or 352
– Bit = 0 → Positive setpoint
– Bit = 1 → Negative setpoint
N_set_A = 4000 hex or 16384 dec = speed in p2000
Parameter
See table "Status word 1"
r0063
r0021
r0068
r0080
r0032
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
Operating
BICO
condition
-
BI: p1035
-
BI: p1036
-
BI: p0810
-
-
Function diagram
FP2452
FP6810
FP6810
FP6850
-
-
SINAMICS DCM Control Module