7.4.3.8

Analog inputs current/voltage switch

Table 7- 30
Current/voltage selector switch S5
7.4.3.9

X522 analog outputs/temperature sensor

Table 7- 31
X522 terminal strip
Terminal
1
2
3
4
5
6
7
8
AO xV: Analog output voltage; AO xC: Analog output current
1)
CAUTION
Permissible back-EMF at the outputs: ±15 V
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
Switch
S5.0
S5.1
Designation
1)
AO 0V+
AO 0-
AO 0C+
AO 1V+
AO 1-
AO 1C+
+ Temp
- Temp
Function
Switchover of voltage (V)/current (I) Al0
Switchover of voltage (V)/current (I) Al1
Technical data
You can set the following output signals using parameters:
Voltage: -10 to 10 V (max. 3 mA)
Current 1: 4 to 20 mA (max. load resistance ≤ 500 Ω)
Current 2: -20 to 20 mA (max. load resistance ≤ 500 Ω)
Current 3: 0 to 20 mA (max. load resistance ≤ 500 Ω)
Resolution: 11 bits + sign
Continuous short-circuit proof
Temperature sensor KTY84-1C130/PTC
Additional system components