Connecting up

4.5 Signaling contact

4.5
Signaling contact
Information on the signaling contact
● To connect the signaling contact, the device has an M12 interface: B-coded, 5-pin, male.
● The signaling contact is a floating switch that signals error statuses by opening the
contact.
The signaling contact must be operated within the range of the operating voltage.
If an error/fault occurs, the signaling contact opens. In normal operation, the signaling
contact is closed.
● To connect the signaling contact, use a copper cable of category 24 AWG or a cable with
a cross-section of ≥ 0.25 mm
NOTICE
Damage due to voltage being too high
You can load the signaling contact with the operating voltage of the device and a maximum
of 100 mA.
Higher voltages or currents can damage the device.
Position and assignment
Figure 4-3
Pin number
1
4
60
, see e.g. the section "Product overview (Page 17)".
2
Position of the signaling contact, for example on the SCALANCE XP208
Contact
F1
F2
Assignment
Fault contact 1
Fault contact 2
Operating Instructions, 05/2016, C79000-G8976-C428-01