Siemens SIMATIC ET 200SP Manual page 25

Analog, ai 2xi 2/4-wire st
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Additional 24 V encoder supply
24 V
Short-circuit protection
Output current, max.
Power loss
Power loss, typ.
Address area
Address space per module
Address space per module, max.
Analog inputs
Number of analog inputs
Permissible input current for current input (de-
struction limit), max.
Cycle time (all channels), min.
Input ranges (rated values), currents
0 mA to 20 mA
Input resistance (0 to 20 mA)
-20 mA to +20 mA
Input resistance (-20 mA to +20 mA)
4 mA to 20 mA
Input resistance (4 mA to 20 mA)
Cable length
Shielded, max.
Formation of analog values for the inputs
Measuring principle
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including sign),
max.
Integration time configurable
Interference voltage suppression for interference
frequency f1 in Hz
Conversion time (per channel)
Measured value smoothing
Number of levels
Configurable
Setting: None
Setting: Weak
Setting: Medium
Setting: Strong
Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1)
Manual, 12/2015, A5E36104399-AA
Technical specifications
6.1 Technical specifications
6ES7134-6GB00-0BA1
Yes
Yes
200 mA; total current for both channels
1.1 W
4 bytes; + 1 byte for QI information
2
50 mA
500 µs
Yes; 15 bits
130 Ω; 90 Ohm with 2 wires
Yes; 16 bits incl. sign
130 Ω; 90 Ohm with 2 wires
Yes; 15 bits
90 Ω; 130 Ohm for 4 wire
1000 m
Sigma Delta
16 bits
Yes
16.6 / 50 / 60 Hz / off
50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6
Hz, 250 µs without filter
4
Yes
Yes; 1 x cycle time
Yes; 4 x cycle time
Yes; 8 x cycle time
Yes; 16 x cycle time
25

Advertisement

Table of Contents
loading

Table of Contents