Interrupts and diagnostic, error, and system alarms
4.3 Alarms
4.3.2

Channel diagnostics

Function
Channel diagnostics provides information about channel faults in modules.
Channel faults are mapped as channel diagnostic data in IO diagnostic data records.
The "RDREC" instruction is used to read the data record.
Structure of the diagnostic data records
The data records supported by the ET 200MP are based on the standard PROFINET IO -
Application Layer Service Definition V2.3.
You can purchase the standard from the PROFIBUS User Organization on the Internet
(http://www.profibus.com).
Codes of the extended channel diagnostics
With the IM 155-5 PN BA interface module, the following extended channel diagnostics are
reported by the Interface module in slot 1:
Table 4- 4
Extended channel diagnostics IM 155-6 PN BA
ChannelError-
ExtendedChan-
Type
nel
ErrorType
0x0601
0x0682
0x0602
0x0692
0x0602
0x0696
0x0602
0x0697
0x0610
0x06B1
0x0610
0x06B2
Additional information
You can find additional information on maximum configuration, power budget and power
segments in the S7-1500, ET 200MP automation system
(https://support.industry.siemens.com/cs/ww/en/view/59191792) system manual.
22
Associated value
Diagnostics
(AddValue)
Slot
Communication has failed with slot <No.>
Slot
Permitted number of I/O modules exceeded
0
No U connector detected on an IM port
0
More than one bus master module (IM/CPU) detected
1
Power budget error (overload has been detected in at least one
(Interface module
power segment)
slot)
0
Error IM power supply: Power supply not active or power sup-
ply active
Interface module IM 155-5 PN BA (6ES7155-5AA00-0AA0)
Manual, 02/2017, A5E38017683-AA