M+Fx5Pg_Startpositioning - Mitsubishi Electric MELSEC iQ-F Manual

Fx5 positioning module function block reference
Hide thumbs Also See for MELSEC iQ-F:
Table of Contents

Advertisement

2.2

M+FX5PG_StartPositioning

Name
M+FX5PG_StartPositioning
Overview
Item
Description
Overview
Starts the positioning operation.
Symbol
(1)
(2)
(3)
(4)
Labels
■Input label
No.
Variable name
Name
(1)
i_bEN
Execution command
(2)
i_stModule
Module label
(3)
i_uAxis
Target axis
(4)
i_uStartNo
Cd.3: Positioning
start No.
■Output label
No.
Variable name
Name
(5)
o_bENO
Execution status
(6)
o_bOK
Normal completion
(7)
o_bErr
Error completion
(8)
o_uErrId
Error code
M+FX5PG_StartPositioning
B
:
i_bEN
DUT
:
i_stModule
UW
:
i_uAxis
UW : i_uStartNo
Data type
Bit
Structure
Word [Unsigned]
Word [Unsigned]
Data type
Bit
Bit
Bit
Word [Unsigned]
o_bENO
:
B
(5)
o_bOK
:
B
(6)
o_bErr
:
B
(7)
o_uErrId
:
UW
(8)
Range
Description
ON, OFF
ON: The FB is activated.
OFF: The FB is not activated.
The setting range
Specifies the module label for the positioning module.
differs depending on
the module label.
1 to 4
Specify the axis number.
The setting range varies according to the positioning
module in use.
1 to 600,
Set the positioning start No. corresponding to the
7000 to 7004,
control to be started in Cd.3: Positioning start No.
9001 to 9004
1 to 600: Positioning data No.
7000 to 7004: Block start specification
9001: Machine OPR
9002: Fast OPR
9003: Current value change
9004: Multiple axes simultaneous start
Default value
Description
OFF
ON: The execution command is ON.
OFF: The execution command is OFF.
OFF
When this label is ON, it indicates that the positioning
operation has been completed.
However, this label does not turn on when a module
error occurs at the start.
OFF
When this label is ON, it indicates that an error has
occurred in the FB.
0
Stores the error code that occurred in the FB.
2.2 M+FX5PG_StartPositioning