5-1. Outdoor Unit
No.
1
Compressor
2
Outdoor fan motor
3
4-way valve coil
4
PMV coil
5
High pressure switch
6
Reactor
7
Reactor
8
Reactor
9
P .C. board (Compressor drive)
10
P .C. board (Fan motor drive)
11
P .C. board (Control)
12
P .C. board (Noise filter)
13
Outdoor temp. sensor (TO sensor)
14
Discharge temp. sensor (TD sensor)
15
Suction temp. sensor (TS sensor)
16
Heat exchanger sensor (TE sensor)
17
Heat exchanger mid. temp. sensor (TL sensor)
18
Fuse
19
Fuse (Mounted on P.C. board, MCC-1596)
20
Fuse (Mounted on P.C. board, MCC-1596)
21
Fuse (Mounted on P.C. board, MCC-1597)
22
Fuse (Mounted on P.C. board, MCC-1597)
23
Fuse (Mounted on P.C. board, MCC-1599)
24
Fuse (Mounted on P.C. board, MCC-1600)
25
Relay
26
Posistor
27
Compressor thermo.
AMP Air Conditioning
5. SPECIFICATIONS OF ELECTRICAL PARTS
Parts name
Type
DA422A3F-27M
ICF-280-A100-1
STF-01AJ502E1
UKV-A038
ACB-4UB83W
CH-78
CH-68
CH-56
MCC-1596
MCC-1597
MCC-1599
MCC-1600
—
—
—
—
—
TLC 10A
GAC1 31.5A
SCT 3.15A
GDM 250V 15A
SCT 3.15A
FJL 250V 3.15A
ET 6.3A
EL200/240A2-F(M)
ZPR0YCE 101A 500
US-622
– 37 –
www.ampair.co.uk | sales@ampair.co.uk
Specifications
—
DC 280 V, 100 W
AC 220 – 240 V, 50/60 Hz
DC 12 V
OFF : 4.15 MPa
4.2 mH, 16 A
18 mH, 5 A
5.8 mH, 18.5 A
—
—
—
—
10 kΩ at 25°C
50 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
10 A, 250 V
31.5 A, 500 V
T3.15 A, AC 250 V
15 A, 250 V
T3.15 A, AC 250 V
T3.15 A, AC 250 V
T6.3 A, AC 250 V
Contact : AC 480 V, 20A
100 Ω, 500 V
OFF : 125 ± 4 °C, ON : 60 ± 5 °C