3. OUTDOOR UNIT REFRIGERATING CYCLE DIAGRAM

Pressure
switch
P
Accumulator
(2500cc)
RAV-SP110 type
(MPa)
Pd
Standard
2.59
Cooling
Overload
3.30
Low load
1.74
Standard
2.35
Heating
Overload
3.22
Low load
2.55
RAV-SP140 type
(MPa)
Pd
Standard
2.77
Cooling
Overload
3.50
Low load
1.75
Standard
2.66
Heating
Overload
3.13
Low load
2.48
RAV-SP160 type
(MPa)
Pd
Standard
2.89
Cooling
Overload
3.61
Low load
1.75
Standard
2.88
Heating
Overload
3.04
Low load
2.48
∗ This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
AMP Air Conditioning
TS sensor
Check joint
Cooling: High pressure
Heating: Low pressure
TD sensor
Muffler
Muffler
Muffler
Ø25 × L180
Ø25 × L210
Rotary compressor
(DA422A3F-27M)
Pressure
(kg/cm²g)
Discharge
Ps
Pd
Ps
(TD)
0.98
26.4
10.0
66
1.09
33.7
11.1
78
0.75
17.8
7.7
46
0.71
24.0
7.2
65
1.17
32.9
11.9
73
0.20
26.0
2.0
99
Pressure
(kg/cm²g)
Discharge
Ps
Pd
Ps
(TD)
0.87
28.3
8.9
74
0.98
35.7
10.0
84
0.76
17.9
7.8
47
0.67
27.1
6.8
75
1.05
31.9
10.7
72
0.20
25.3
2.0
98
Pressure
(kg/cm²g)
Discharge
Ps
Pd
Ps
(TD)
0.78
29.5
8.0
81
0.90
36.8
9.2
88
0.77
17.9
7.9
48
0.65
29.4
6.6
82
1.05
31.0
10.7
71
0.20
25.3
2.0
98
TO sensor
TL sensor
TE sensor
Heat exchanger
Distributor
Ø8, 2 rows, 52 stages
FP1.45, flat fin
In cooling operation
In heating operation
Strainer
Pipe surface temperature (°C)
Indoor heat
Outdoor heat
Suction
exchanger
exchanger
(TS)
(TC)
(TL)
13
13
44
9
13
49
7
5
32
3
39
7
19
54
14
–23
45
–19
Pipe surface temperature (°C)
Indoor heat
Outdoor heat
Suction
exchanger
exchanger
(TS)
(TC)
(TL)
12
10
46
10
14
54
8
6
33
2
44
7
16
53
12
–23
44
–19
Pipe surface temperature (°C)
Indoor heat
Outdoor heat
Suction
exchanger
exchanger
(TS)
(TC)
(TL)
10
9
48
11
15
57
9
7
33
2
47
7
16
52
12
–23
44
–19
– 35 –
PMV
Strainer
Capillary
Ø4 ×Ø3 (6 pcs.)
Refrigerant pipe
at liquid side Ø9.5
Packed valve
Refrigerant pipe
at gas side Ø15.9
Ball valve
Cooling: Low pressure
Heating: High pressure
Compressor
drive revolution
Indoor
frequency
fan
(rps)
(TE)
42
40
HIGH
43
53
HIGH
25
21
LOW
3
43
HIGH
15
26
LOW
–19
96
HIGH
Compressor
drive revolution
Indoor
frequency
fan
(rps)
(TE)
42
54
HIGH
46
64
HIGH
25
21
LOW
3
55
HIGH
13
26
LOW
–19
96
HIGH
Compressor
drive revolution
Indoor
frequency
fan
(rps)
(TE)
43
65
HIGH
49
74
HIGH
26
21
LOW
3
63
HIGH
13
26
LOW
–19
96
HIGH
www.ampair.co.uk | sales@ampair.co.uk
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
30/–
24/18
15/–
–15/–
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
30/–
24/18
15/–
–15/–
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
30/–
24/18
15/–
–15/–

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents