TABLE 11: Electrical Data For Multi-source Power Supply: 208/230-1-60
Air Handlers Models
Heater Models
6HK16501306
6HK16501506
25B
6HK16501806
6HK16502006
6HK16501306
6HK16501506
37B
6HK16501806
6HK16502006
6HK16501306
6HK16501506
37C
6HK16501806
6HK16502006
38B
6HK16501306
6HK16501506
38C
6HK16501806
6HK16502006
6HK16501306
6HK16501506
49C
6HK16501806
6HK16502006
6HK16501306
6HK16501506
49D
6HK16501806
6HK16502006
6HK16502506
6HK16501306
6HK16501506
50C
6HK16501806
6HK16502006
6HK16501306
6HK16501506
50D
6HK16501806
6HK16502006
6HK16502506
6HK16501306
6HK16501506
61C
6HK16501806
6HK16502006
6HK16501306
6HK16501506
61D
6HK16501806
6HK16502006
6HK16502506
NOTES:
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or
in Canada the Canadian electrical Code and local codes to determine correct wire sizing.