Purpose of the Heat
Pump

2.1 Application

The hydro tower constitutes the interface between a non-revers-
ible heat pump and the heat distribution in the building. The
hydro tower contains all hydraulic components required between
heat generation and heat distribution with an unmixed heating
circuit. A dual differential pressureless manifold with a buffer tank
allows an energy-optimised hydraulic integration of the heat gen-
erator and the heat distribution.
NOTE
The device is not suitable for operation with a frequency converter.

2.2 General properties

Low installation effort
All components easily accessible
Ready-to-connect, contains all essential components, i.e.
pumps, shut-offs, safety devices and heat pump manager
Integrated hot water cylinder
Integrated buffer tank reduces operating cycles of the heat
pump, thus increasing the efficiency of the system
The infinitely adjustable operation of the circulating pump in
the heating circuit allows the output to be adjusted according
to need.
Pipe heater for supplementary heating.
3

Scope of supply

3.1 Basic device

Hydraulic components
Buffer tank, 60 litres
Unmixed heating circuit with overflow valve
Primary circuit of heat generation including circulating pump,
shut-offs and reversing valve for domestic water preparation
2nd heat generator, electrical pipe heater, heat output 2 kW,
secured via safety temperature limiter
200 litre hot water cylinder
Safety equipment:
Safety valve, start-to-leak pressure 2.5 bar
An additional expansion vessel can be connected

3.2 Switch box

ATTENTION!
Before opening the device, ensure that all circuits are powered down.
The switch box is located in the upper area of the hydro tower.
After removing the front cover, the switch box is freely accessi-
ble.
The switch box contains the supply connection terminals, heating
contactors, Bus connections (connecting line to the heat pump)
and the heat pump manager (HWK 230 Econ5S).

3.3 Heat pump manager

The integrated heat pump manager (WPM Econ5S) is a conven-
ient electronic regulation and control device. It controls and mon-
itors the entire heating system based on the external tempera-
ture, as well as domestic hot water preparation and safety
systems.
The external temperature sensor (to be connected on site) in-
cluding the fixing accessories, is included in the scope of supply
of the heat pump manager.
The enclosed operating instructions describe the function and
use of the heat pump manager.
452162.66.15 · FD 9701