Internal and external site door requirements

Internal site doorways must obey the following height requirements:
For the 642 1075 mm rack — no less than 200.19 cm (78.816 in)
For the 642 1200 mm rack — no less than 200.66 cm (79.00 in)
To account for the lifted height of the pallet, external doorways must obey the following height
requirements:
For the 642 1075 mm rack — no less than 216.80 cm (85.35 in)
For the 642 1200 mm rack — no less than 215.00 cm (84.65 in)
More information
Generic Site Preparation Guide

Electrical specifications

Table 4: Enclosure power options
Source type
3–phase
3–phase
Single-phase
Table 5: Single-phase power cords
Part number
8120-6895
8120-6897
8121-0070
8120-6903
Source voltage
Plug or
(nominal)
connector type
200 VAC to 240
NEMA L15-30p,
VAC line-to-line
3-Pole, 4-wire,
(phase-to-
3 m (10 ft)
phase), 3-
power cord
phase
50/60 Hz
220 VAC to 240
IEC 309, 4-
VAC line-to-
pole, 5-wire,
neutral 3-phase
Red, 3 m (10 ft)
power cord
50/60 Hz
200 VAC to 240
IEC 320
VAC
C19-C20
50/60 Hz
Description
Stripped end, 240 V
Male IEC309, 240 V
Male GB-1002, 240 V
Male NEMA L6-20, 240 V
Circuit type
Power
receptacle
required
30 A 3-phase
L15-30R. 3-
pole, 4-wire
16 A
IEC 309, 4-
pole, 5-wire, red
16/20 A Single-
IEC 320
phase
C19
Where used
International - other
International
China
North America/Japan
Internal and external site door requirements
Number of
power cords
required (per
enclosure)
4
4
12
25