Table 8: Enclosure 3-phase 2400 W power supply specifications (International)
Specification
Power cords (4)
Max input current per line cord
Output
Input requirements
Rated input voltage
Rated input frequency
Maximum inrush current
Ground leakage current
Power factor correction
Table 9: Enclosure power requirements
Power required (50–60 Hz)
User expected maximum power
1
Typical maximum power or user expected maximum power (input power at the AC input expressed in
watts and volt-amps). This figure was developed with the absolute maximum configuration running
applications designed to draw the maximum power possible. It is highly unlikely that any real-world
application will result in this amount of power use for any significant time period.
Table 10: Enclosure PDU power options
Source/Circuit
Source voltage
type
(nominal)
3–phase 60 A
200–240 VAC line-
to-line (phase-to-
phase), 3–phase
50/60 Hz
3–phase 32 A
220–240 VAC line-
to-neutral 3–phase
50/60 Hz
1
Plug or connector
type
IEC 309 60 A 3-
Pole, 4 wire, Blue,
3.6 m (11.8 ft)
power cord
IEC 309 32 A 4-
Pole, 5 wire, Red,
3.6 m (11.8 ft)
power cord
Value
IEC-309 220–240 VAC, 5-pin, 16 A
3.0 m (10 ft)
12.1 A at 220 VAC
11.1 A at 240 VAC
2450 W per power supply
200–240 VAC line-to-neutral 3-phase
50-60 Hz
100 A for 10 ms
3.5 mA
0.98
Watts
9065
Power receptacle
Number of power
required
cords required
(per enclosure
leaving the rack)
IEC 309 60 A 3-
2
Pole, 4 wire, Blue
IEC 309 32 A 4-
2
Pole, 5 wire, Red
System specifications
VA
9250
Table Continued
27