6. Technical data

Operating voltage:
Frequency:
Power consumption:
Standby output:
Switch output:
Voltage at sensor input:
Contact:
Contact gap:
Max switching capacity:
switching capacity:
Sensor type:
sensor length:
Mode of operation:
Operating temperature:
Protection class:
Protection rating:
Time accuracy (typical):
Power reserve:
Pollution degree:
Rated impulse withstand voltage: 4 kV
230V AC, +10 % / -15 %
50–60 Hz
1,4 W
1,36 W
switching of any phase is
permitted
Safety Extra-Low Voltage
(SELV) approx. 3.5 V
Changeover contact
<3 mm (μ)
10 A/ 250 V~, cos ϕ = 1;
2 A/ 250 V~, cos ϕ = 0,6
10 mA/230 V AC
100 mA/12 V AC/DC
NTC,
max. 50 m
type 1 B in accordance
with 60730-1
0 °C ... +50 °C
II in accordance with EN
60730-1 subject to cor-
rect installation
IP 20 in accordance with
EN 60529
≤ ± 0.25 s/day (25 °C)
10 years at +20 °C
2