Flue, Flexible, System Size 80 And 100 (Components) (Type B; Plastic (Pps) Flue Pipe For Routing The Flue Over External Walls - Viessmann Vitoladens 300-C Technical Manual

Flue systems for oil condensing boilers
Table of Contents

Advertisement

Design and sizing information for the Vitoladens 300-C, -T, and Vitorondens 200-T, 222-F

Flue, flexible, system size 80 and 100 (components) (type B

E
9
7
C
6
E
A
D
8
1
E
Illustration with the Vitoladens 300-C
A Ventilation air aperture, min. 150 cm
B Flue gas
C Inspection port
D Connection piece = ¼ of the vertical length or max. 3 m
E Secondary ventilation
Note
Install the flexible flue with a maximum offset of 45° from the vertical.
2.6 Plastic (PPs) flue pipe for routing the flue over external walls (type B
VITOLADENS, VITORONDENS
B
2
5
C
3
2
4
2
2
2
2
2
or 2 × 75 cm
2
to TRÖI 2009)
23
Rated heating output (kW)
1 Boiler flue connection (part of the stand-
ard boiler delivery)
2 Standard shaft pack (PPs, flexible)
Comprising:
– Support bend
– Support rail
– Shaft cover (PPs)
– Spacers (5 pce, max. clearance 2 m)
or
Standard shaft pack (metal/PPs, flexi-
ble)
For twin flue chimneys; one flue for solid
fuel boilers.
Comprising:
– Support bend
– Support rail
– Shaft cover (metal)
– Terminal pipe (stainless steel)
– Spacers (5 pce, max. clearance 2 m)
Spacers (5 pce, max. clearance 2 m)
3 Flue pipe, flexible, as a 12.5 or 25 m roll
4 Connection piece for connecting residual
lengths of the flexible flue
Pipe lowering attachment with 25 m
rope
5 Inspection piece, straight (1 pce) for
installation into the flexible flue
6 Inspection piece, straight (1 pce)
7 Ventilation bezel (1 pce)
8 Pipe
1 m long (1 pce)
0.5 m long (1 pce)
9 Bend
87º (1 pce)
45º (2 pce)
or
Inspection bend 87º (1 pce)
Inspection tee 87º (1 pce)
Stainless steel extension, 380 mm long
for shaft cover, metal/PPs, flexible
Max. total flue length: 18 m
The following components are taken into consideration for the maxi-
mum flue lengths:
■ Connection pipe D 0.5 m long.
■ 1 bend 87º and 1 support bend 87º
or
■ 2 bends 45º and 1 support bend 87º
Subtract other bends, tees and extension pieces from the maximum
length using the following values:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
■ Bend 45º: 0.3 m
■ Bend 87º: 0.5 m
■ Inspection tee: 0.3 m
The Vitoladens may also be connected, without shaft, to a flue pipe
that is routed over an external wall.
(cont.)
up to
from
35.4
42.8
System size
Ø mm
80
100
80
100
80
100
80
100
80
100
80
100
80
100
80
100
80
100
80
100
80
100
80
100
100
80
80
100
to TRÖI 2009)
23
VIESMANN
23
2