Design and sizing information for the Vitoladens 300-C, -T, and Vitorondens 200-T, 222-F
Flue, flexible, system size 80 and 100 (components) (type B
E
9
7
C
6
E
A
D
8
1
E
Illustration with the Vitoladens 300-C
A Ventilation air aperture, min. 150 cm
B Flue gas
C Inspection port
D Connection piece = ¼ of the vertical length or max. 3 m
E Secondary ventilation
Note
Install the flexible flue with a maximum offset of 45° from the vertical.
2.6 Plastic (PPs) flue pipe for routing the flue over external walls (type B
VITOLADENS, VITORONDENS
B
2
5
C
3
2
4
2
2
2
2
2
or 2 × 75 cm
2
to TRÖI 2009)
23
Rated heating output (kW)
1 Boiler flue connection (part of the stand-
ard boiler delivery)
2 Standard shaft pack (PPs, flexible)
Comprising:
– Support bend
– Support rail
– Shaft cover (PPs)
– Spacers (5 pce, max. clearance 2 m)
or
Standard shaft pack (metal/PPs, flexi-
ble)
For twin flue chimneys; one flue for solid
fuel boilers.
Comprising:
– Support bend
– Support rail
– Shaft cover (metal)
– Terminal pipe (stainless steel)
– Spacers (5 pce, max. clearance 2 m)
Spacers (5 pce, max. clearance 2 m)
3 Flue pipe, flexible, as a 12.5 or 25 m roll
4 Connection piece for connecting residual
lengths of the flexible flue
Pipe lowering attachment with 25 m
rope
5 Inspection piece, straight (1 pce) for
installation into the flexible flue
6 Inspection piece, straight (1 pce)
7 Ventilation bezel (1 pce)
8 Pipe
1 m long (1 pce)
0.5 m long (1 pce)
9 Bend
87º (1 pce)
45º (2 pce)
or
Inspection bend 87º (1 pce)
Inspection tee 87º (1 pce)
Stainless steel extension, 380 mm long
for shaft cover, metal/PPs, flexible
Max. total flue length: 18 m
The following components are taken into consideration for the maxi-
mum flue lengths:
■ Connection pipe D 0.5 m long.
■ 1 bend 87º and 1 support bend 87º
or
■ 2 bends 45º and 1 support bend 87º
Subtract other bends, tees and extension pieces from the maximum
length using the following values:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
■ Bend 45º: 0.3 m
■ Bend 87º: 0.5 m
■ Inspection tee: 0.3 m
The Vitoladens may also be connected, without shaft, to a flue pipe
that is routed over an external wall.