PLANNING YOUR INSTALLATION
Clearan ces t o co m b u st ib les are d et erm in ed f ro m t est in g t o ap p licab le st an d ard s f o r allo w -
able heat transfer. The clearances allowed as shown here, do not take into account operation
o r serviceab ilit y req u iremen t s.
MASONRY AND ZERO CLEARANCE
FIREPLACES
The model Profile
30 INS is approved for installation
into a solid fuel burning fireplace, either a masonry fire-
place or an approved factory-built / zero clearance fire-
place (see pages 18 and 19 for additional information on
venting).
Dimensions Into a Fireplace
Height
Width @ Front
(extends back 1 ½")
Width @ back
Depth
CAUTION: The fireplace in which the Profile
INS is to be installed must be thoroughly cleaned if
it has been used to burn wood or synthetic logs.
Have the chimney and all inside surfaces of the
fireplace brushed and vacuumed so that no soot,
embers, or loose combustion deposits can be
drawn into the heat circulation blower and blown
into the living area. If any portion of the chimney
system shows signs of structural or mechanical
weaknesses, such as: cracks, leaky joints, corroded
or warped surfaces, the faulty portion must be re-
paired or replaced prior to installing this appliance.
IMPORTANT: When installing the Profile
into a factory built fireplace, the firebox must accept
the insert without modification other than removing
bolted or screwed together pieces such as smoke
shelf / deflectors, ash lips, screen or door tracks
and damper assemblies. Any fireplace component
which is removed must be retained so they can be
reinstalled to restore the fireplace to its original op-
erating condition. The removal of any part must not
alter the integrity of the outer shell of the pre-
engineered fireplace cabinet in any way.
20 1/8" / 512 mm
32"
/ 814 mm
24 5/8" / 626mm
17 ¾" / 452 mm
30 INS
HEARTH REQUIREMENTS / FLOOR PROTECTION
   
Profile
30 INS
The area directly in front of the Profile
protected by a noncombustible material or a fireplace
hearth or hearth extension as follows:
Combustible flooring must be protected by non-
combustible material in Canada and 10 millimeter (3 / 8
inches) millboard or equivalent non-combustible in
U.S. extending beneath the heater and to the front as
indicated or to the nearest permitted combustible ma-
terial. See page 5 for requirements when using alter-
nate material as hearth extension.
The protected area must extend 6" to the front of the face
of the Profile
MINIMUM CLEARANCES TO
COMBUSTIBLES
A - Insert to side wall
B - Insert to side trim
C - Hearth extension
D - Insert to mantel
E - Insert to top trim
30
PAGE 7
30 INS.
inches / millimeters
6" / 153 mm
1" / 26 mm
6" / 153 mm
18" / 458 mm
1" / 26 mm
Top View
Side View
30 INS must be