Vivax ACP-12CT32AEI/I Service Manual page 50

Table of Contents

Advertisement

MCAC-UTSM-2008-04
7. P2 malfunction
Judge 1: The wiring between the low pressure switch and main
control board is connected well or correctly
Judge 2: Whether the low pressure switch is broken
Validate: Short connect the low pressure switch
socket, check whether the system can run normally
Check whether the refrigerant system is ok
Judge 3: Check whether the outdoor ambient
temperature is too low
Judge 4: The refrigerant of the system is leakage
Validate: Connect the pressure gauge to the gauge joint of the
system, check whether the pressure is lower than 0.15MPa
Judge 5: The refrigerant pipe is blocked
Outdoor Units
PDF 文件使用 "pdfFactory Pro" 试用版本创建
LED indicates P2
Low pressure protection
Yes
No
No
No
No
Replace outdoor main board
No
Yes
Replace low pressure switch
Yes
Leak hunting: charge nitrogen or
refrigerant to the system, if the leakage is
serious, there will be distinct gas leakage
"cici" sound; if the leakage is little, use
the suds(mixture of water and abluent is
Yes
also ok, if it can make bubble) or
electronic leak detector.
Drop refrigerant, then use the high pressure
Yes
nitrogen or refrigerant to blow pipe, vacuumize
and add the refrigerant again
www.fineprint.cn
Troubleshooting
Connect it well
Stop the unit
53