3. SIGNALS AND WIRING

3.11 Servo amplifier terminal block (TE2) wiring method

(1) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is. (Cable size: 0.2 to
2.5mm
)
2
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder
the core as it may cause a contact fault. (Cable size: 0.2 to 2.5mm
terminal may be used to put the wires together.(Phoenix contact make)
(Bar terminal ferrule with insulation sleeve)
Bar terminal for 1 cable
Cable size
2
[mm
]
AWG
For 1 cable
Al0.25-6YE
0.25
24
Al0.25-8YE
Al0.5-6WH
0.5
20
Al0.5-8WH
Al0.75-6GY
0.75
18
Al0.75-8GY
Al1-6RD
1
18
Al1-8RD
Al1.5-6BK
1.5
16
Al1.5-8BK
Al2.5-8BU
2.5
14
Al2.5-8BU-1000
Approx. 10mm
Bar terminal for 2 cable
(Twin ferrule with insulation sleeve)
Bar terminal type
For 2 cables
Al-TWIN2
0.75-8GY
Al-TWIN2
0.75-10GY
Al-TWIN2
1-8RD
Al-TWIN2
1-10RD
Al-TWIN2
1.5-8BK
Al-TWIN2
1.5-12BK
Al-TWIN2
2.5-10BU
Al-TWIN2
2.5-13BU
3 - 57
)Alternatively, a bar
2
Crimping
tool
CRIMPFOX-UD6