3.4.2 Configuration as a detector line

3.4.2.1 Collective detectors which can be connected

Building Technologies
Fire Safety
The information in this chapter applies to the following types of detector line:
Collective detector lines
Collective detector lines for areas at risk of explosion
Conventional detector lines
A short-circuit on the detector line is never evaluated as an alarm. The
functionality 'short-circuit = alarm' is not supported.
It is not possible to operate collective detectors and conventional detectors
simultaneously on the same detector line.
Different generations of detector can be connected to the input/output module:
Detectors on the collective detector line:
Cerberus FIT 110 series
MS9 fire detection system
SIGMACON fire detection system
AlgoRex fire detection system
Synova 600 series fire detector
Special detectors on the collective detector line:
MS24, AlgoRex, and Sinteso/Cerberus PRO flame detector
AlgoRex and Sinteso/Cerberus PRO linear detector
Sinteso/Cerberus PRO neural fire detector
Titanus ProSens smoke extraction system (only with new resetting board
type E548/c, order number 09-20-5481)
AlgoRex and Sinteso/Cerberus PRO point detector and manual call point
for potentially explosive atmospheres
Not all detectors are always supported by the fire detection systems mentioned.
The information in the 'List of compatibility' is key to ascertaining compatibility:
For fire detection systems FS20: Document 008331
For fire detection systems
FS720:
Input/output configuration options (secondary side)
Document A6V10229261
Structure and function
33 | 72
009122_h_en_--
2016-05-04