Panasonic FP0R User Manual page 10

Hide thumbs Also See for FP0R:
Table of Contents

Advertisement

Differences between specifications of FP0 and FP0R effecting program change
Change in
As the size of the data area and the settings of hold and non-hold areas changes,
data areas
check if the address of the used data memory is correct. The area that has been used
as a hold area might be a non-hold area.
The following instructions that are supported on the FP0 cannot be used. Replace
Change in
them with the instructions for the FP0R based on the following description.
supported
[FP0]
instructions
F144(TRNS) instruction
F168(SPD1) instruction
F169(PLS) instruction
F170(PWM) instruction
As for the following instructions, the specifications change. Modify the programs in
accordance with the specifications after the change.
[FP0]
F12(ICRD) instruction
Unit of read: 64 words
P13(PICWT) instruction
Unit of write: 64 words
Change in
The addresses of the following special internal relays are changed.
special
High-speed counter control flag
internal
[FP0]
R903A: For CH0
relays
R903B: For CH1
R903C: For CH2
R903D: For CH3
Change in
The contents of the following special data registers are changed.
special data
[FP0]
registers
DT9052(DT90052):
High-speed counter control flag
As each 4 bits of the control code for all
4 channels are allocated, write the
control code in the area of the
corresponding channel.
The addresses of the following special data registers are changed.
Elapsed value of high-speed counter CH0 to CH3
[FP0]
DT9044(DT90044)-DT9045(DT90045)
DT9048(DT90048)-DT9049(DT90049)
DT9104(DT90104)-DT9105(DT90105)
DT9108(DT90108)-DT9109(DT90109)
Target value of high-speed counter CH0 to CH3
[FP0]
DT9046(DT90046)-DT9047(DT90047)
DT9050(DT90050)-DT9051(DT90051)
DT9106(DT90106)-DT9107(DT90107)
DT9110(DT90110)-DT9111(DT90111)
Note) The numbers in parentheses are for FP0-T32.
viii
[FP0R]
F159(MTRN) instruction
F171(SPDH), F177(HOME) instructions
F172 (PLSH) instruction
F173(PWMH) instruction
[FP0R]
Unit of read: 2048 words
Unit of write: 2048 words
[FP0R]
→ R9110 : For CH0
→ R9111 : For CH1
→ R9112 : For CH2
→ R9113 : For CH3
[FP0R]
DT90052:
High-speed counter control flag
As the areas to write the channel numbers
to be changed and the control codes are
separated, write the corresponding channel
numbers and control codes.
[FP0R]
→DT90300-DT90301
→DT90304-DT90305
→DT90308-DT90309
→ DT90312-DT90313
[FP0R]
→ DT90302-DT90303
→ DT90306-DT90307
→ DT90310-DT90311
→ DT90314-DT90315