20. Quick Reference Guide - Error Codes

LED Display (LED 1: Blue)
Slow Flash
On
Fast Flash
Slow flash -- flashing at 1Hz.
Fast flash - flashing at 2Hz.
Main Control
IPM Control (comp. driver)
Blue LED
Red LED
Slow Flash
OFF
ON
ON
Fast Flash
OFF
Fast Flash
ON
Fast Flash
Fast Flash
Fast Flash
Fast Flash
Fast Flash
ON
Fast Flash
OFF
Fast Flash
Fast Flash
Slow flash - Flashing at 1Hz
Fast flash- Flashing at 2Hz
Display
Error Description
E0
Outdoor unit EEPROM error.
E2
Communication error between outdoor unit and all indoor units.
E3
Communication error between outdoor unit main control and IPM control.
E4
Temperature sensor error (outdoor coil, outdoor ambient , compressor discharge and indoor unit coil outlet temperature sensors.
E5
High and low voltage protection.
E8
Outdoor DC fan speed error.
F1
Indoor unit #1 coil outlet temperature sensor error.
F2
Indoor unit #2 coil outlet temperature sensor error.
F3
Indoor unit #3 coil outlet temperature sensor error.
F4
Indoor unit #4 coil outlet temperature sensor error.
F5
Indoor unit #5 coil outlet temperature sensor error.
F6
Indoor unit #6 coil outlet temperature sensor error.
P1
High pressure switch open
P2
Low pressure switch open
P3
Outdoor compressor current overload sensed.
P4
High temperature sensed at compressor discharge line.
P5
High temperature sensed at outdoor coil.
P6
Inverter module (IPM) error.
Table 6.
Single-Zone 009/012 115VAC/208-230VAC
Table 7.
Single-Zone 018/030 208-230VAC
Error Description
Green LED
ON
Stand-by
OFF
Normal operation
ON
Could be one of the following:
ON
DC bus voltage is too high or to low protection.
ON
Driver EEPROM error.
OFF
Driver chip start-up failure.
Fast Flash
Could be one of the following:
Fast Flash
IGBT over-current or IPM over-current
Fast Flash
Control chip communication error.
Table 8.
Multi-Zone Outdoor Unit
Error Description
Standby
Normal operation
Outdoor unit error.
Indoor and outdoor unit communication error.
Outdoor unit temperature sensor error.
Outdoor unit EEPROM error
Compressor top temperature switch is open.
Driver phase loss protection
Driver zero speed protection
PWM synchronization failure.
95