NOTE - Extremes of operating range are plus and minus 10% of line voltage. HACR type circuit breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Lennox Mini-Split Service Manual / Page 12...
NOTE - Extremes of operating range are plus and minus 10% of line voltage. HACR type circuit breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Lennox Mini-Split Service Manual / Page 13...
NOTE - Extremes of operating range are plus and minus 10% of line voltage. HACR type circuit breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Lennox Mini-Split Service Manual / Page 14...
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE - Adaptors are furnished for the gas pipe connections: 018 - (2) 3/8 x 1/2 in. 030 - (3) 3/8 x 1/2 in. Lennox Mini-Split Service Manual / Page 16...
036 - (3) 3/8 x 1/2 in. and (1) 1/2 x 3/8 in. 048 - (3) 3/8 x 1/2 in., (2) 1/2 x 3/8 in., (2) 1/4 x 3/8 in. and (2) 1/2 x 5/8 in. Lennox Mini-Split Service Manual / Page 17...
2007 Clearance dimensions apply to both single-fan cabinets and double-fan cabinets. Minimum rear clearance can be 6 inches (152 mm) when mounted on brackets and with no obstructions on the other three sides. Lennox Mini-Split Service Manual / Page 49...
SECTION 4.5 - MCFA CEILING/FLOOR UNIT Lennox Mini-Split Service Manual / Page 63...
Page 64
2 (51) Piping 2-1/4 (57) Condensate Drain Refrigerant Outlets (2) each side BOTTOM VIEW Piping Opening 4-3/4 x 5-1/2 (121 x 140) Model No. 42-1/8 1070 50-5/8 1286 47-3/8 1203 1651 61-3/4 1568 Lennox Mini-Split Service Manual / Page 64...
Page 65
SIDE VIEW SUPPLY CEILING AND FLOOR APPLICATIONS WALL WALL 24” (610) (610) FRONT VIEW FLOOR APPLICATIONS Unit Flush with Wall SUPPLY 24” (610) (Service Clearance Front of Unit) 1” (25.4) FLOOR SIDE VIEW Lennox Mini-Split Service Manual / Page 65...
9,954 9,954 - - - One outdoor unit may be matched with one indoor unit for single zone applications. A second indoor unit can be added at a later date for multi-zone applications. Lennox Mini-Split Service Manual / Page 67...
Page 68
- - - - - - One outdoor unit may be matched with one indoor unit for single zone applications. A second indoor unit can be added at a later date for multi-zone applications. Lennox Mini-Split Service Manual / Page 68...
012 012 012 012 012 10,306 10,306 10,306 10,306 10,306 11,055 11,055 11,055 11,055 11,055 One outdoor unit may be matched with one indoor unit for single zone applications. A second indoor unit can be added at a later date for multi-zone applications. Lennox Mini-Split Service Manual / Page 69...
82 ft. (25 m) 82 ft. (25 m) 164 ft. (50 m) 98 ft. (30 m) 98 ft. (30 m) 213 ft. (65 m) 98 ft. (30 m) 98 ft. (30 m) 213 ft. (65 m) Lennox Mini-Split Service Manual / Page 79...
SECTION 6.2 - REFRIGERATION PIPE WORK FOR MULTI-ZONE SYSTEMS Lennox Mini-Split Service Manual / Page 80...
Page 81
Set Elevation 3-Zone 82 ft. (25 m) Indoor Units 4-Zone 98 ft. (30 m) Below Outdoor Unit INDOOR UNIT 4-Zone 98 ft. (30 m) 33 ft. (10 m) INDOOR UNIT Five-Zone System Example shown Lennox Mini-Split Service Manual / Page 81...
1/2 x 5/8 in. gas pipe adaptor is required for line set connection to the 048 1/2 x 5/8 in. gas pipe adaptor is required for line set connection to the 048 outdoor unit (furnished with outdoor unit). outdoor unit (furnished with outdoor unit). Lennox Mini-Split Service Manual / Page 82...
1/2 x 5/8 in. gas pipe adaptor is required for line set connection to the 048 1/2 x 5/8 in. gas pipe adaptor is required for line set connection to the 048 outdoor unit (furnished with outdoor unit). outdoor unit (furnished with outdoor unit). Lennox Mini-Split Service Manual / Page 83...
(furnished with outdoor unit). outdoor unit (furnished with outdoor unit). 1/2 x 5/8 in. gas pipe adaptor is required for line set connection to the 048 outdoor unit (furnished with outdoor unit). Lennox Mini-Split Service Manual / Page 84...
115V MPA009S4S-1L and MPA012S4S-1L Outdoor Unit Wiring Diagram PAN HEATER CRANKCASE CN34 CN15 HEATER CN33 CN32 CN31 CN28 VALVE CN26 YELLOW BLUE BROWN BLUE L-A(CN37) CN10 POWER SUPPLY BLACK Typical wiring diagram. Refer BLACK 115V to wiring diagram on the unit for actual wiring.
208/230V MPA024S4S-1P Outdoor Unit Wiring Diagram Compressor L-OUT COMPRESSOR DISCHARGE Control Board TEMP.SENSOR CN10 YELLOW PAN HEATER CRANK CASE HEATER Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. Lennox Mini-Split Service Manual / Page 90...
P O W E R S U P P LY 4 WAY VALVE OUTDOOR COIL TEMP. SENSOR OUTDOOR TEMP. SENSOR Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. Lennox Mini-Split Service Manual / Page 92...
DCFAN2 DCFAN1 NOTE Please use 2-core COMP shielded wire. BLUE CN17 4-WAY CN18 BLUE CN24 HEAT_Y CN25 CN19 HEAT_D CN20 Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. Lennox Mini-Split Service Manual / Page 93...
EXPANSION CN11 VALVE CN12 BLUE 1(A) 3(A) 2(A) 1(B) 2(B) 3(B) 1(C) 2(C) 3(C) 4 WAY CRANKCASE HEATER VALVE HEATER Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. Lennox Mini-Split Service Manual / Page 95...
C N 2 4 HEA T_Y C N 2 5 C N 1 9 HEA T_D C N 2 0 Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. Lennox Mini-Split Service Manual / Page 96...
MWMA Unit Wiring Diagram CN10A CN3(CN301) CN501 Contoller CN403 OPTIONAL DISPLAY BOARD Wire Contoller Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. To CCM Comm.Bus Lennox Mini-Split Service Manual / Page 98...
WHITE CN13 MAINBOARD PUMP WATER LEVEL SWITCH CN110 E Y X Typical wiring diagram. Refer to wiring diagram on the unit for actual 1 2 3 wiring. To CCM Comm.Bus TO OUTDOOR UNIT Lennox Mini-Split Service Manual / Page 99...
INDOOR COIL OUTLET TEMP.SENSOR Reactor INDOOR COIL TEMP.SENSOR BLACK ROOM TEMP.SENSOR WHITE WATER LEVEL SWITCH Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. To CCM POWER Comm.Bus To OUTDOOR Comm.Bus Lennox Mini-Split Service Manual / Page 100...
INDOOR COIL OUTLET TEMP. SENSOR Typical wiring diagram. Refer to wiring diagram on WATER LEVEL SWITCH the unit for actual wiring. BLACK BLACK FILTER-BOARD To CCM To outdoor Comm.Bus Comm.Bus POW ER SUPPLY Lennox Mini-Split Service Manual / Page 101...
INDOOR COIL TEMP. SENSOR WHITE ROOM TEMP. SENSOR Typical wiring diagram. WATER LEVEL SWITCH Refer to wiring diagram on YELLOW the unit for actual wiring. BLACK BLACK FILT ER- B OA RD To CCM Comm.Bus Lennox Mini-Split Service Manual / Page 102...
BLACK FILTER-BOARD Ferrite bead Remote Alarm Control Output To CCM Comm.Bus • • • • • To outdoor This symbol indicates the element is Comm.Bus optional,the actual shape shall prevail. Lennox Mini-Split Service Manual / Page 103...
Comm.Bus • • • • • This symbol indicates the element is To outdoor Comm.Bus optional,the actual shape shall prevail. Typical wiring diagram. Refer to wiring diagram on the unit for actual wiring. Lennox Mini-Split Service Manual / Page 104...
1 inch (25 mm) drain holes and attached a fi eld-provided insulated drain hose to the connector. Use fi eld-provided rubber plugs to cover any unused drain holes. Condensate Drain Drain (location varies per model) Chassis Connector Lennox Mini-Split Service Manual / Page 107...
MAIN DRAIN (Sloped at 1/4” per foot AWAY from unit and should be supported as needed to prevent sagging.) Condensate Drain Multiple Indoor Units Suspended from Ceiling Using a Single Properly Sloped Gravity Drain Lennox Mini-Split Service Manual / Page 109...
(ground, open drain, etc.) to ensure that the line will drain freely. STRUCTURAL CEILING 8 in. 3 ft. (1 m) (203 mm) SUSPENSION RODS SUPPORT STRAPS DRAIN LINE Condensate Drain with Pump Lennox Mini-Split Service Manual / Page 111...
7-7/8in. 2~3-15/16 in. 3 ft. (1 m) Cassette SUPPORT Unit STRAPS Drain (slope of at least ¼ inch per foot) Indoor Unit Condensate Drain Lennox Mini-Split Service Manual / Page 112...
Page 115
• Turns the LCD display backlight on the indoor unit SPEED” or “ON/OFF” buttons. on or off. NOTE - SLEEP mode is only available when the unit is in COOL, HEAT or AUTO mode. Lennox Mini-Split Service Manual / Page 115...
Page 116
After approximately 2 seconds, the signal “H” will disappear and the set temperature will re-appear on the LCD display window. Lennox Mini-Split Service Manual / Page 116...
Page 118
RESET LOCK ECONOMY RESET FAN SPEED SELECTION LOCK MODE Button • Select system operation modes. Push button to cycle through each setting. AUTO COOL HEAT POWER Button • Turns system on and off. Lennox Mini-Split Service Manual / Page 118...
The capacity unit is horse power. If the indoor unit is not connected, the digital display tube will show: “――” C indoor unit capacity (9K:1HP,12K:1.2HP,18K:1.5HP) D indoor unit capacity E indoor unit capacity Lennox Mini-Split Service Manual / Page 121...
Page 122
D indoor unit evaporator temp. show “70”. If the indoor unit is not connected, the digital display tube (T2D) will show: “――” E indoor unit evaporator temp. (T2E) Condenser pipe temp.(T3) Outdoor ambient temp.(T4) Lennox Mini-Split Service Manual / Page 122...
Page 123
The last error or protection 00 means no malfunction and protection code F indoor unit capacity F Indoor unit capacity demand code F indoor unit evaporator outlet temp.(T2BF) F indoor unit room temp.(T1F) Lennox Mini-Split Service Manual / Page 123...
Page 124
Display Remark F indoor unit evaporator temp. (T2F) EXV open angle for F indoor unit Lennox Mini-Split Service Manual / Page 124...
When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or alternative displays between running frequency and “E6”(each displays 0.5s) In protection or malfunction, the LED displays error code or protection code. Lennox Mini-Split Service Manual / Page 125...
Page 127
All other indoor units have digital displays on either the unit front cover or inside the control box or flash code displays on the main control board. Section 13.5 contains troubleshooting information for all Multi-Zone outdoor units • Multi-Zone outdoor units display a digital readout on the main control board. Lennox Mini-Split Service Manual / Page 127...
Single Zone 009/012 115VAC/208-230VAC Outdoor Units Quick Reference Error Description Outdoor Unit Sticker Shown - See Indoor Unit for Error Code Lennox Mini-Split Service Manual / Page 129...
Control board chip communication error Fast flash Fast flash Fast flash NOTE Slow flash----Flashing at 1Hz Fast flash----Flashing at 2Hz IDU--Indoor unit ODU---Outdoor unit Outdoor Unit Sticker Shown - See Indoor Unit for Error Code Lennox Mini-Split Service Manual / Page 130...
Outdoor Compressor current overload sensed High temperature sensed at compressor discharge line High temperature sensed at outdoor coil Inverter module (IPM) error Outdoor Unit Sticker Shown - See Indoor Unit for Additional Error Code Information Lennox Mini-Split Service Manual / Page 131...
Mode conflict Compressor high-pressure or low-pressure switch open Indoor Unit Sticker Shown - ALL Indoor Units 09/24 Display NOTE flash , light, X extinguished Indoor Unit Sticker Shown - ALL Indoor Units 09/30-48 Lennox Mini-Split Service Manual / Page 132...
SECTION 13.2 - TROUBLESHOOTING SINGLE ZONE OUTDOOR UNITS Lennox Mini-Split Service Manual / Page 133...
Page 134
PWM synchronization failure Fast flash IGBT over-current/IPM over-current Fast flash Control board chip communication error Fast flash Fast flash Fast flash NOTE Slow flash----Flashing at 1Hz Fast flash----Flashing at 2Hz IDU--Indoor unit ODU---Outdoor unit Lennox Mini-Split Service Manual / Page 134...
Page 135
Fault Code LED Illustrative Drawing of Board Shown - Actual Unit May Differ MPA009S4S-1L and MPA012S4S-1L Lennox Mini-Split Service Manual / Page 135...
Page 136
KFR 26W $BP2- 180( D YD C - 390- N 3) . D . 13. W P2. 1 Power ON Fault Code LEDs Illustrative Drawing of Board Shown - Actual Unit May Differ MPA009S4S-1P and MPA012S4S-1P Lennox Mini-Split Service Manual / Page 136...
Page 137
C E- KFR 72W / BP3( 2) - 350( 311+0515+1246+STK5C 4U 341/ 340) . D . 13. W P2. 1 Fault Code LEDs Illustrative Drawing of Board Shown - Actual Unit May Differ MPA018S4S-1P Lennox Mini-Split Service Manual / Page 137...
Page 138
CompTop LOW/HIGH IC16 CN25 IC12 CONdebug1 IC13 L-OUT 4-WAY FUSE1 HEAT1 T5A 250VAC L-IN HEAT2 PTC1 CN29 202302130895 N-OUT CE-KFR80W/BP3T4N1(DC MOTOR)-310.D.03.WP1-1 N-IN Illustrative Drawing of Board Shown - Actual Unit May Differ MPA024S4S-1P Lennox Mini-Split Service Manual / Page 138...
Page 139
C 60 C 11 202302141206 EU - KFR 105W / BP3T5N 1- 350S. D . 13. W P1- 1 Fault Code LEDs Illustrative Drawing of Board Shown - Actual Unit May Differ MPA030S4S-1P Lennox Mini-Split Service Manual / Page 139...
SECTION 13.3 - TROUBLESHOOTING MULTI- ZONE OUTDOOR UNITS Lennox Mini-Split Service Manual / Page 140...
Page 141
Indoor unit #6 coil outlet temp. sensor error High pressure switch open Low pressure switch open Outdoor Compressor current overload sensed High temperature sensed at compressor discharge line High temperature sensed at outdoor coil Inverter module (IPM) error Lennox Mini-Split Service Manual / Page 141...
Page 142
MPA030S4M-1P Shown - Actual Unit May Differ Lennox Mini-Split Service Manual / Page 142...
PCB main chip does not receive feedback from EEPROM chip. EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the below photos. Lennox Mini-Split Service Manual / Page 143...
E0 Flow Chart Outdoor EEPROM malfunction Power off, then restart the unit 3 minutes later. Does the problem still exist? Replace the outdoor main PCB. Outdoor PCB(M3OC-30HRFN1-M) Lennox Mini-Split Service Manual / Page 144...
Communication malfunction between outdoor unit and all indoor units. General Note: Indoor unit does not receive the communication from outdoor unit for 120 seconds or outdoor unit does not receive the communication from any one indoor unit for 180 seconds. Lennox Mini-Split Service Manual / Page 145...
(2 for 2-zone, 3 for Problem Solved 3-zone, 4 for 4-zone). Refer PIC 4. No fi rst time No second time Change outdoor unit PCB as- sembly totally (include wiring). Lennox Mini-Split Service Manual / Page 146...
Page 147
When AC is normal running, the voltage will move alternately between positive value and negative value. Pic 2: IPM (for 2-zone/3-zone) Power (some Power (some models) modles) Self-Check OK Opera ng Pic 2 Lennox Mini-Split Service Manual / Page 147...
Page 148
Pic 3: Main board LED when power on and unit standby. Pic 4: Check point button, press 1 time to check how many indoor units are connected. Lennox Mini-Split Service Manual / Page 148...
E3 Fault Code Basic Description: Communication error between outdoor unit main control and IPM. General Note: PCB main chip does not receive feedback from IPM during 60 seconds. Lennox Mini-Split Service Manual / Page 149...
Replace IPM board, and then check whether the system can run normally. Replace outdoor main board, and then check whether the system can run nor- mally. Problem Solved. Replace the electric control box. Lennox Mini-Split Service Manual / Page 150...
Page 151
The normal value should be around 5V. Use a multimeter to test the DC voltage between black pin and red pin of signal wire. The normal value should be around 12V.. Lennox Mini-Split Service Manual / Page 151...
Basic Description: Temp. sensor error (outdoor coil sensor, outdoor ambient sensor, compressor discharge sensor, indoor unit coil outlet temp. sensor) General Note: Error displays if voltage is lower than 0.06V or higher than 4.94V. Lennox Mini-Split Service Manual / Page 152...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 153...
E5 Fault Code Basic Description: High or low voltage protection General Note: An abnormal voltage rise or drop is detected by checking the specifi ed voltage detection circuit. Lennox Mini-Split Service Manual / Page 154...
18-27KBtu/h; DC277-410V for 36KBtu/h. Replace bridge rectifi ers, and then check whether the system can run normally(Only for 4-zone) Replace IPM board, and then check for normal unit operation Replace outdoor main board. Problem Solved. Lennox Mini-Split Service Manual / Page 155...
Page 156
IPM (for 2-zone and 3-zone) IPM (for 4-zone) P-N (for 2-zone and 3-zone) Lennox Mini-Split Service Manual / Page 156...
PFC module protection. (For MPA036S4M-1P and MPA048S4M-1P) General Note: When the voltage signal that PFC sends to main control board is abnormal, the display LED will show “E6” and AC will turn off. Lennox Mini-Split Service Manual / Page 160...
Check if the inductance of the PFC module is good. If the inductor is Replace the inductor. good, the resistance value of the two ports is 0. Replace the PFC module. Problem Solved. Lennox Mini-Split Service Manual / Page 161...
Page 162
Inductor Two terminals of the inductor Lennox Mini-Split Service Manual / Page 162...
Page 163
Lennox Mini-Split Service Manual / Page 163...
Outdoor DC fan motor speed error. General Note: When outdoor fan speed keeps too low (300RPM) or too high(2400RPM) for certain time, the unit will stop and the LED will display the failure. Lennox Mini-Split Service Manual / Page 164...
Wheel and shaft should spin evenly and balanced. Check all wiring connections. Correct faulty corrections. Check main PCB, see index 1. Replace the main PCB. Replace the fan motor. Lennox Mini-Split Service Manual / Page 165...
Page 166
If the value of the voltage is not in the range shown in below table, the PCB faulty and should be replaced. DC motor voltage input and output Color Signal Voltage Vs/Vm 200~380V Black White 13.5~16.5V Yellow 0~6.5V Blue 13.5~16.5V Lennox Mini-Split Service Manual / Page 166...
Page 167
Lennox Mini-Split Service Manual / Page 167...
F1 Fault Code Basic Description: Indoor unit #1 coil outlet temp. sensor error General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 168...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 169...
F2 Fault Code Basic Description: Indoor unit #2 coil outlet temp. sensor error General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 170...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 171...
F3 Fault Code Basic Description: Indoor unit #3 coil outlet temp. sensor error General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 172...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 173...
F4 Fault Code Basic Description: Indoor unit #4 coil outlet temp. sensor error General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 174...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 175...
F5 Fault Code Basic Description: Indoor unit #5 coil outlet temp. sensor error General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 176...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 177...
P1 Fault Code Basic Description: High pressure switch open. General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 179...
Check if the outdoor fan runs properly outdoor fan motor. Check outdoor coils. The outdoor unit coils should be Clean outdoor coils. clean and free of any debris. Replace outdoor main board. Check whether the refrigerant system is OK. Lennox Mini-Split Service Manual / Page 180...
Page 181
Lennox Mini-Split Service Manual / Page 181...
P2 Fault Code Basic Description: Low pressure switch open General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 182...
Fully open the high pressure valve. Refer to the solution of fan speed mal- function (E8). Find out the cause correct Check if the indoor fan runs properly in cooling mode. Replace outdoor main board. Lennox Mini-Split Service Manual / Page 183...
Page 184
Lennox Mini-Split Service Manual / Page 184...
P3 Fault Code Basic Description: Outdoor compressor current overload sensed General Note: If the outdoor current exceeds the current limit value, the LED will display the failure. Lennox Mini-Split Service Manual / Page 185...
Perform proper vacuum procedures, then Judge 5: The refrigerant pipe is blocked. restart system. Replace outdoor main board, and check whether the system can run normally. Replace the electric control box. Problem Solved. Lennox Mini-Split Service Manual / Page 186...
Page 187
Lennox Mini-Split Service Manual / Page 187...
High temperature sensed at compressor discharge line. General Note: When the compressor discharge temperature(T5) is more than 115°C for 10 seconds, the compressor will stop and restart till T5 is less than 90°C. Lennox Mini-Split Service Manual / Page 188...
Measure the resistance value of compressor dis- Replace the compressor charge temp. sensor. If the value is not normal is discharge temp. sensor. normal refer to the Appendix 2? Replace outdoor main PCB. Replace high pressure valve assy. Lennox Mini-Split Service Manual / Page 189...
Basic Description: High temperature sensed at outdoor coil. General Note: When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temperature is less than 52°C. Lennox Mini-Split Service Manual / Page 190...
Confi rm if system has the correct refrigerant charge. Remove remaining refrigerant charge, pressure test and locate Replace the outdoor main board. leak. Add correct charge. Test system. If system fails to operate correctly replace outdoor board. Lennox Mini-Split Service Manual / Page 191...
Basic Description: Inverter module (IPM) error. General Note: When the voltage signal that IPM sends to the compressor drive chip is abnormal, the display LED will show “P6” and AC will turn off. Lennox Mini-Split Service Manual / Page 192...
(for M4OC- 36HRFN1-M& M4OC- 36HRDN1-M) Replace the wir- ing or reactor or Replace the compressor, replace the PFC check whether the system module(for M4OC- operates normally? 36HRFN1-M) Problem Solved Lennox Mini-Split Service Manual / Page 193...
SECTION 13.4 - INDOOR UNIT FAULT CODES Lennox Mini-Split Service Manual / Page 194...
Page 195
Mode conflict Compressor high-pressure or low-pressure switch open Indoor Unit Sticker Shown - ALL Indoor Units 09/24 Display NOTE flash , light, X extinguished Indoor Unit Sticker Shown - ALL Indoor Units 09/30-48 Lennox Mini-Split Service Manual / Page 195...
Page 196
OPERATION indication lamp: This lamp illuminates when the air conditioner is in operation. TIMER indication lamp: Lights up during Timer operation. Temperature indicator: Displays the temperature settings when the air conditioner is operational. Displays the malfunction code. Wall-Mounted Unit Lennox Mini-Split Service Manual / Page 196...
E0 Fault Code Basic Description: Indoor unit EEPROM error General Note: PCB main chip does not receive communication from EEPROM chip. Lennox Mini-Split Service Manual / Page 197...
Is it still displaying the error code? If the EEPROM chip is soldered on PCB, re- Insert the EEPROM properly place the PCB. Otherwise, check whether the EEPROM chip is plugged in PCB properly? Replace the indoor PCB. Lennox Mini-Split Service Manual / Page 198...
E1 Fault Code Basic Description: Communication malfunction between indoor unit and outdoor unit. General Note: PCB main chip does not receive feedback from IPM module during 60 seconds. Lennox Mini-Split Service Manual / Page 199...
Replace IPM board, and then check whether the system can run normally. Replace outdoor main board, and then check whether the system can run nor- mally. Problem Solved. Replace the electric control box. Lennox Mini-Split Service Manual / Page 200...
Page 201
The normal value should be around 5V. Use a multimeter to test the DC voltage between black pin and red pin of signal wire. The normal value should be around 12V.. Lennox Mini-Split Service Manual / Page 201...
E3 Fault Code Basic Description: Indoor fan speed error. General Note: When indoor fan speed runs too low (300RPM) for a certain time, the unit will stop and the LED will display the error. Lennox Mini-Split Service Manual / Page 202...
Correct the connections. connected correctly? Measure the voltage for the fan motor from the main PCB. Is the voltage cor- rect? Replace the electric control box. Replace the main PCB Replace the fan motor Lennox Mini-Split Service Manual / Page 203...
E4 Fault Code Basic Description: Indoor return air temperature sensor error. General Note: If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error. Lennox Mini-Split Service Manual / Page 204...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 205...
E5 Fault Code Basic Description: Indoor Coil Temperature Sensor Error General Note: If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error. Lennox Mini-Split Service Manual / Page 206...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 207...
If the temperature of T2 drops per this formula three times in the fi rst 5 minutes of operation, the system shuts down and the error code displays. For this formula “Tcool” = the T2 temperature at startup. T2 < Tcool - 3.6°F (2°C) Lennox Mini-Split Service Manual / Page 208...
Check to see if cool air is blowing out of it functioning the indoor air outlet Replace the indoor PCB Check for refrigerant leaks. Repair leaks and re- charge system. Check for restriction in refrigerant lines. Clear restriction. Lennox Mini-Split Service Manual / Page 209...
EE Fault Code Basic Description: Water-level alarm malfunction. (For cassette/A5 duct) General Note: If the sampling voltage is not 5V, the LED will display the failure. Lennox Mini-Split Service Manual / Page 210...
If the water-level switch is inserted well? switch well. Replace the water-level If the water-level switch is broken? switch. Replace the water pump, If malfunction is still not solved. Replace the indoor main PCB. Lennox Mini-Split Service Manual / Page 211...
F0 Fault Code Basic Description: Outdoor compressor current overload sensed General Note: If the outdoor current exceeds the current limit value, the LED will display the failure. Lennox Mini-Split Service Manual / Page 212...
Perform proper vacuum procedures, then Judge 5: The refrigerant pipe is blocked. restart system. Replace outdoor main board, and check whether the system can run normally. Replace the electric control box. Problem Solved. Lennox Mini-Split Service Manual / Page 213...
F1 Fault Code Basic Description: Outdoor Temperature Sensor T4 Error. General Note: If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error. Lennox Mini-Split Service Manual / Page 214...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 215...
F2 Fault Code Basic Description: Faulty Outdoor Coil Temperature Sensor T3/T5. General Note: If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error. Lennox Mini-Split Service Manual / Page 216...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 217...
Basic Description: Compressor discharge temperature sensor error General Note: When the compressor discharge temperature(T5) is more than 115°C for 10 seconds, the compressor will stop and restart till T5 is less than 90°C. Lennox Mini-Split Service Manual / Page 218...
Measure the resistance value of compressor dis- Replace the compressor charge temp. sensor. If the value is not normal is discharge temp. sensor. normal refer to the Appendix 2? Replace outdoor main PCB. Replace high pressure valve assy. Lennox Mini-Split Service Manual / Page 219...
PCB main chip does not receive feedback from EEPROM chip. EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the below photos. Lennox Mini-Split Service Manual / Page 220...
F4 Flow Chart Outdoor EEPROM malfunction Power off, then restart the unit 3 minutes later. Does the problem still exist? Replace the outdoor main PCB. Outdoor PCB(M3OC-30HRFN1-M) Lennox Mini-Split Service Manual / Page 221...
Basic Description: Outdoor unit fan speed error General Note: When outdoor fan speed keeps too low (300RPM) or too high(2400RPM) for certain time, the unit will stop and the LED will display the failure. Lennox Mini-Split Service Manual / Page 222...
Wheel and shaft should spin evenly and balanced. Check all wiring connections. Correct faulty corrections. Check main PCB, see index 1. Replace the main PCB. Replace the fan motor. Lennox Mini-Split Service Manual / Page 223...
F6 Fault Code Basic Description: Indoor Unit Evaporator Outlet Coil Temperature Sensor Faulty General Note: If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error. Lennox Mini-Split Service Manual / Page 224...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- door PCB. Is it normal? Replace the sensor. Lennox Mini-Split Service Manual / Page 225...
IPM module or IGBT overcurrent protection. General Note: When the voltage signal that IPM sends to the compressor drive chip is abnormal, the display LED will show “P6” and AC will turn off. Lennox Mini-Split Service Manual / Page 226...
(for M4OC- 36HRFN1-M& M4OC- 36HRDN1-M) Replace the wir- ing or reactor or Replace the compressor, replace the PFC check whether the system module(for M4OC- operates normally? 36HRFN1-M) Problem Solved Lennox Mini-Split Service Manual / Page 227...
P1 Fault Code Basic Description: High or Low voltage protection General Note: An abnormal voltage rise or drop is detected by checking the specifi ed voltage detection circuit. Lennox Mini-Split Service Manual / Page 228...
18-27KBtu/h; DC277-410V for 36KBtu/h. Replace bridge rectifi ers, and then check whether the system can run normally(Only for 4-zone) Replace IPM board, and then check for normal unit operation Replace outdoor main board. Problem Solved. Lennox Mini-Split Service Manual / Page 229...
The outdoor unit will resume operation when either: The OUTDOOR temperature is higher than -7.6°F (-22°C) for 10 minutes and compressor has been stopped for 1 hour Outdoor temperature is higher than 23°F (-5°C) for 10 minutes Lennox Mini-Split Service Manual / Page 230...
P4 Fault Code Basic Description: Compressor drive error General Note: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and etc Lennox Mini-Split Service Manual / Page 232...
PCB. Refer to the fault code fan speed malfunc- Check the outdoor fan and the outdoor unit ventilation. tion (E8). Check the compressor resistance values. Replace the compressor. Replace the outdoor main PCB. Lennox Mini-Split Service Manual / Page 233...
B will change to stand by and A will be no change. Cooling mode Heating mode Cooling Mode Heating Mode No = No mode confl ict. Yes = Mode confl ict Lennox Mini-Split Service Manual / Page 234...
Compressor high-pressure or low-pressure switch open General Note: If the sampling voltage of pressure switch is not 5V, the LED will display the failure. Test each pressure switch separately following these fl ow charts. Lennox Mini-Split Service Manual / Page 235...
Check if the outdoor fan runs properly outdoor fan motor. Check outdoor coils. The outdoor unit coils should be Clean outdoor coils. clean and free of any debris. Replace outdoor main board. Check whether the refrigerant system is OK. Lennox Mini-Split Service Manual / Page 236...
Page 237
Fully open the high pressure valve. Refer to the solution of fan speed mal- function (E8). Find out the cause correct Check if the indoor fan runs properly in cooling mode. Replace outdoor main board. Lennox Mini-Split Service Manual / Page 237...
Page 238
Lennox Mini-Split Service Manual / Page 238...
P7 Fault Code Basic Description: Outdoor IGBT temperature sensor error General Note: If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error. Lennox Mini-Split Service Manual / Page 239...
PCB. Are the connec- tions good? Check the resistance value of the sensor via Appendix 1 and Appendix 2. Replace indoor or out- Is it normal? door PCB. Replace the sensor. Lennox Mini-Split Service Manual / Page 240...
Measure the resistance value of each winding by using the tester. This can also be used to check for shorted compressor windings, and identifying terminals when they are no longer legible. Position Resistance Value DA150S1C-20FZ DA250S2C-30MT TNB306FPGMC-L MNB36FAAMC-L Blue - Red 0.95Ω (20°C/68°F) 0.55Ω (20°C/68°F) 0.53Ω (20°C/68°F) 0.44Ω (20°C/68°F) Lennox Mini-Split Service Manual / Page 244...
Use a digital tester to measure the resistance between P and UVWN; UVW and N. Normal Normal Resistance Digital Tester Digital Tester Resistance Value Value (+)Red (-)Black (+)Red (-)Black ∞ ∞ (Several MΩ) (Several MΩ) (+)Red Lennox Mini-Split Service Manual / Page 245...
If the value of the voltage is not in the range, the PCB must have problems and need to be replaced. 2 Turn off the power, use a digital tester to measure the resistance. The value should be 1.8~2.5 KΩ. Lennox Mini-Split Service Manual / Page 247...
EXV Check Disconnect the connectors. Resistance to EXV Coil Color of lead wire Normal Value Red- Blue Red - Yellow About 50Ω Brown-Orange Brown-White Lennox Mini-Split Service Manual / Page 248...
Page 249
Red- Blue Red - Yellow Lennox Mini-Split Service Manual / Page 249...
NOTE - If the low voltage protection occurs and not resumes within 3 minutes, it will keep the protection always after restart the machine. VOLTAGE No limit VOLT_RST1_ADD VOLT_LTM1_ADD VOLT_LTM_FREQ1_ADD VOLT_RST2_ADD VOLT_LTM2_ADD VOLT_LTM_FREQ2_ADD Lennox Mini-Split Service Manual / Page 251...
If 215.6°F (102°C) < T5 < 244.4°F (115°C), decrease the frequency to the lower level every two minutes until to F1. If T5 < 244.4°F (115°C) for ten seconds, the compressor will stop and restart till T5 < 194°F (90°C) Lennox Mini-Split Service Manual / Page 252...
When T4< 37.4°F (3°C) and the compressor is not running for 3 hours, the crankcase heater will be active. Preheating Release If T4>41°F (5°C) or the indoor has capacity demand, the crankcase heater will stop Condition work. Lennox Mini-Split Service Manual / Page 253...
17°C - 25°C <17°C Cooling >77°F 62.6°F - 77°F <62.6°F Modify Rate 100% NOTE - The fi nal result is integer. In low ambient cooling mode, modify rate is fi xed as 40%. Lennox Mini-Split Service Manual / Page 254...
Page 255
NOTE - Average value of T2: Sum T2 value of all indoor units)/ (indoor units number). According to the fi nal capacity request to confi rm the operating frequency, as following table. Heating capacity improved in low ambient heating Lennox Mini-Split Service Manual / Page 255...
Defrost mode ends when any of the following conditions are met. 1. T3 > 64.4°F (18°C) 2. T3 remains > 43.4 °F (8°C) for 80 seconds 3. System has been in defrost mode for 10 minutes Lennox Mini-Split Service Manual / Page 256...
T3. When T3≥38°C (100.4°F) or when T4≥20°C (68°F), the outdoor fan will choose the speed according to T4 again. Exit low ambient cooling mode run with high fan for 1 minute Lennox Mini-Split Service Manual / Page 257...
16p close; If average+2≥the T2≥ average-2, the relevant valve’s open range remains; If the T2<average-2, the relevant valve needs more 16p open. This modifi cation will be carry out every 2 minutes. Lennox Mini-Split Service Manual / Page 258...