Indoor Unit Lift Pump - Lennox MPA009S4S Service Manual

Mini-split systems
Table of Contents

Advertisement

Indoor
Unit
Figure 52. Condensate Drain Multiple Indoor Units Suspended from Ceiling Using a Single Properly Sloped

14.3. Indoor Unit Lift Pump

14.3.1. Condensate Piping Requirements - MMDA and M22A/M33A/M33B
14.3.1.1 MMDA
Make sure that drain piping is properly routed and insulated in order to prevent both leaks and condensation.
Drain should have a slope of at least ¼ inch per foot and should be approved corrosion-resistant pipe. You must confirm
operation of every drain and pump in the system as part of the commissioning procedure.
1. Use a field-provided hose clamp to secure the drain line stub on the side of the unit chassis to a field-supplied 1" (25
mm) drain line. See figure below.
NOTE:
Take care not to over-tighten the hose clamps this may damage the drain line stub.
2. Make a water-tight connection between the field-provided condensate drain line and the flexible condensate connector.
Use 1-1/2" OD / 1-1/4" ID PVC pipe for the drain line.
3. See figure for applications including an indoor unit using the internal drain pump.
4. In all cases, drain should be as short as possible and should not have any droops or kinks that would restrict condensate
flow and shall be constructed using an approved pipe. There must be a 2-inch (51 mm) space between the end of
the condensate drain and the final termination point (ground, open drain, etc.) to ensure that the line will drain
freely.
Indoor
Unit
INDIVIDUAL DRAIN OUTLET FROM EACH INDOOR UNIT
CAUTION
IMPORTANT
FLEXIBLE DRAIN
INDOOR
UNIT
CONDENSATE
HOSE CLAMP
LINE STUB
Figure 53. Condensate Piping Connection
Indoor
Unit
(Sloped at 1/4" per foot AWAY from unit and should
be supported as needed to prevent sagging.)
Gravity Drain
PVC DRAIN
CONNECTOR
PIPE
INSULATION
79
MAIN DRAIN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents