11.5 Accessories technical data

11.5.1 Water coil for reheating
Section 1.03 Coil code
Geometry
Tubes per row
Rows
Fin pitch
Capacity
Outlet temp
Air pressure drop
Water pressure drop
Size valued in the following hypothesis:
Water 70/60°C;
Air entrance temperature 8°C;
Nominal air volume.
11.5.2 Electrical reheating
Coil code
Electrical coil 1 stage
Power supply
Phases
Stage
Absorbed current
Outlet Air Temp (+)
(+) Size valued with Ting air = 8°C and nominal air capacity.
18
SKW 10
SKW 14
25 22
N °
14
N °
3
mm
2.5
KW
9.4
° C
36
Pa
65
kPa
8
SKE 03
SKE 06
kW
2
4
V
230
230
1
1
1
1
A
8.7
17.4
°C
28.4
27.8
SKW 19
25 22
25 22
14
16
3
3
2.5
2.5
13.4
16.6
36.6
34.1
64
85
16
10
SKE 10
SKE 14
4.5
6
400
400
3
3
1
1
6.5
8.7
21.3
20.7
SKW 25
SKW 30
25 22
25 22
17
17
3
3
2.5
2.5
23.9
28.4
36.6
34.5
62
85
11
15
SKE 19
SKE 25
SKE 30
9
12
12
400
400
400
3
3
3
1
1
1
13
17.3
17.3
22
22.2
19.5
IOM / MINIAIR-0507
SKW 40
25 22
21
3
2.5
36.2
34.3
92
27
SKE 40
12
400
3
1
17.3
17