Radiation Fin Temperature Rise - Daikin ATXS35EV1B7 Service Manual

Inverter pair e-series
Hide thumbs Also See for ATXS35EV1B7:
Table of Contents

Advertisement

Troubleshooting
4.22

Radiation Fin Temperature Rise

4.22.1 25/35 Class
L4
Remote
Controller
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
compressor on.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
116
If the radiation fin temperature with the compressor on is above 90°C.
Clearing condition : when the temperature drops below 85°C.
If a radiation fin temperature rise takes place 4 times successively, the system will be shut
down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Silicon grease is not applied properly on the heat radiation fin after replacing outdoor unit
PCB
SiBE04-824
Service Diagnosis