DETAILS OF INPUT AND OUTPUT SIGNALS
Device No.
Signal
RWw10,
RWw12,
Link parameter
RWw14,
extended setting/
RWw16,
Instruction code
RWw18
RWw11,
RWw13,
RWw15,
Write data
RWw17,
RWw19
66
Set the instruction code (refer to page 71) for execution of operation mode rewrite,
Pr. read/write, error reference, error clear, etc. The instructions are executed in the
following order by setting "1" in RYF after completing the register setting: RWw2,
10, 12, 14, 16, then 18. After completing the execution up to RWw18, "1" is set in
RXF. Set HFFFF to disable an instruction by RWw10 to 18. (RWw2 is always
executed.)
The first 8bits are link parameter extended setting.
Example) When reading Pr. 160, instruction code is H0200.
Set the data specified by the instruction code of RWw10, 12, 14, 16, and 18. (when
required)
RWw10 and 11, 12 and 13, 14 and 15, 16 and 17, and 18 and 19 correspond each
other.
Set "1" in RYF after setting the instruction codes (RWw10, 12, 14, 16, and 18) and
the corresponding register.
Set zero when the write code is not required.
Description