Mitsubishi Electric FR-A7NC Instruction Manual page 66

Plug-in option
Hide thumbs Also See for FR-A7NC:
Table of Contents

Advertisement

Device
No.
Frequency setting completion/torque
RXD
command setting completion
*4
(RAM)
Frequency setting completion/torque
RXE
command setting completion
*4
(RAM, EEPROM)
RXF
Instruction code execution completion
*4
RX1A
Error status flag
RX1B
Remote station ready
*3
Torque command can be set for the FR-A700 series only.
*4
When Pr.544 = "100", RXC to RXF are remotely input available with the programmable controller function. (FR-A700
series NA/EC version only)
For details, refer to the FR-A700 programmable controller function programming manual.
Signal
After "1" is set in the frequency setting command/torque command
(RYD) and the frequency setting command/torque command is
written to the inverter RAM, "1" is set in this signal.
*3
When "0" is set in the frequency setting command/torque
command (RYD), "0" is set in this signal.
After "1" is set in the frequency setting command/torque command
(RYE) and the frequency setting command/torque command is
written to the inverter RAM and EEPROM, "1" is set in this signal.
*3
When "0" is set in the frequency setting command/torque command
(RYE), "0" is set in this signal.
After "1" is set in the instruction code execution request (RYF) and
the processes corresponding to the instruction codes (RWw2, 10,
12, 14, 16 and 18) are executed, "1" is set in this signal.
When "0" is set in the instruction code execution request (RYF), "0"
is set in this signal.
When an inverter error occurs (protective function is activated), "1"
is set in this signal.
When the inverter goes into the ready status upon completion of
initial setting after power-on or hardware reset, "1" is set in this
signal. When an inverter error occurs (protective function is
activated), "0" is set in this signal.
The signal is used as an interlock signal during the write to/read
from the master module.
DETAILS OF INPUT AND OUTPUT SIGNALS
Description
7
59

Advertisement

Table of Contents
loading

Table of Contents