Diagnostics, wire break (in current mode)
When this parameter is enabled, the Wire break diagnostics event is generated when a wire
break is detected. This diagnostics event cannot be detected in the zero range.
Diagnostics, short circuit (in voltage mode)
If you enable this parameter, a diagnostics event is generated in the event of a short circuit
in the output line. This diagnostics event cannot be detected in the zero range.
Diagnostics, overload
If you enable this parameter, the diagnostics event is generated in the event of an overload.
Substitute values
With this parameter, you enter a substitute value that the module is to output in CPU-STOP
mode. The substitute value must be in the nominal range, overrange, or underrange.
11.2.4

Output ranges of analog output device

Output ranges for voltage and current: ±10 V; ±20 mA
Output range
Output range
±10 V
0.00 V
11.76 V
23.52 mA
10 V
7.5 V
361.7 μV
723.4 nA
0 V
-361.7 μV
-723.4 nA
-7.5 V
-10 V
-11.76 V
-23.52 mA
0.00 V
ET 200eco PN
Operating Instructions, 06/2009, A5E01250250-04
±20 mA
Decimal
0.00 mA
20 mA
15 mA
0 mA
-15 mA
-20736
-20 mA
-27648
-32512
0.00 mA
-32768
Units
32767
32512
32511
27649
27648
20736
1
0
-1
-27649
-32513
I/O device analog input/output
11.2 I/O device analog output
Hexadecimal
7FFF
Overflow
H
7F00
H
7EFF
Overrange
H
6C01
H
6C00
Nominal range
H
5100
H
0001
H
0000
H
FFFF
H
AF00
H
9400
H
93FF
Underrange
H
8100
H
80FF
Underflow
H
8000
H
Range