6. Click Corr. Input (zero). The following advisory message will be displayed:
The PV Input (Zero) refers to a known standard such as zero pressure (e.g.: vent both
sides of a DP transmitter). As indicated below, this procedure will shift the slope up or down to
eliminate the error at the zero reference. The slope (angle) of the response is unchanged.
7. Click Yes in the Correct Input message box, and you will be prompted to Apply the PV
Input (Zero) now.
8. Verify that the value of the PV applied at the input is exactly Zero. Then click OK to send
the Correct Input (Zero) command to the Transmitter, which adjusts the input calibration.
9. Wait for the message Sensor input has stabilized, then click OK.
10. When the zero correction is complete, the message Sensor zero succeeded! is displayed;
click the OK button.
Page 60
ST 700 Series HART/DE Option User's Manual