CHILLER PROTECTIVE LIMIT FAULTS (continued)
ICVC
PRIMARY MESSAGE SECONDARY
FAULT
STATE
243
POTENTIAL FREEZE-
UP
244
POTENTIAL FREEZE-
UP
245
PROTECTIVE LIMIT
246
PROTECTIVE LIMIT
247
PROTECTIVE LIMIT
248
PROTECTIVE LIMIT
249
PROTECTIVE LIMIT
250
UNUSED
251
PROTECTIVE LIMIT
252
PROTECTIVE LIMIT
253
PROTECTIVE LIMIT
254
PROTECTIVE LIMIT
255
PROTECTIVE LIMIT
256
PROTECTIVE LIMIT
257
PROTECTIVE LIMIT
258
UNUSED STATE
259
PROTECTIVE LIMIT
282
PROTECTIVE LIMIT
283
PROTECTIVE LIMIT
284
VFD GATEWAY
285
VFD GATEWAY
286
PROTECTIVE LIMIT
*
[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., setpoint predefined or selected by the operator as an override, alert, or alarm condition.
[VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
6
Table 10 - Alarm and alert messages (continued)
ALARM MESSAGE PRIMARY
MESSAGE
CAUSE
EVAP PRESS/TEMP
243->Evaporator Refrig Temp
TOO LOW
[VALUE] exceeded limit of [LIMIT]*.
COND PRESS/TEMP
244->Condenser Refrig Temp
TOO LOW
[VALUE] exceeded limit of [LIMIT]*.
HIGH VFD SPEED
245->Actual VFD Speed exceeded
limit of Target VFD Speed ± 10%]*.
INVALID DIFUSER
246->Diffuser Control Invalid Con-
CONFIG.
figuration: Check SETUP2 Entries
DIFFUSER
247->Diffuser Position Fault: Check
POSITION FAULT
Guide Vane/Diffuser Actuators
SPARE
248->Spare Temperature #1
TEMPERATURE #1
[VALUE] exceeded limit of [LIMIT]*.
SPARE
249->Spare Temperature #2
TEMPERATURE #2
[VALUE] exceeded limit of [LIMIT]*.
UNUSED
250->Unused state
VFD CONFIG
251->VFD Config Conflict (VFD
CONFLICT
Uploaded); Verify to Reset Alarm.
VFD CONFIG
252->VFD Config Conflict (VFD
CONFLICT
Downloaded); Verify to Reset Alarm.
GUIDE VANE
253->Guide Vane Fault [VALUE].
CALIBRATION
Check Calibration
VFD CHECKSUM
254->Checksum Error: Press Reset
ERROR
to Restore Configuration
VFD DEW
255->VFD Dew Prevention - VFD
PREVENTION
Coolant too Cold, Check Solenoid
and Cond T
INDUCTOR
256->Inductor Overtemp Trip - Check
OVERTEMP
Temp Switch and Cooling Fans
VFD START INHIBIT
257->VFD Start Inhibit: Check VFD
Diagnostic Parameters 212/214.
UNUSED
258->Unused
CCN OVERRIDE
259->CCN Emergency/Override
STOP
Stop.
INVALID VFD
282->Line Frequency [VALUE]
CONFIG
Exceeded Configuration Range.
INVALID VFD
283->Compressor 100%
CONFIG
Speed Config Ranges: 50=Hz
45-52; 60 Hz=55-62.
COMPATIBILITY
284->VFD Gateway Compatibil¬ity
CONFLICT
Conflict: Check VFG/VFD Versions.
COMPATIBILITY
285->VFD Gateway Compatibil¬ity
CONFLICT
Conflict: Check VFG/ICVC Versions.
INVERTER
286->Inverter Overcurrent Fault:
OVERCURRENT
Check VFD Status.
ADDITIONAL CAUSE/REMEDY
Check for proper refrigerant charge.
Check float valve operation.
Check for proper fluid flow and temperature.
Confirm that condenser water enters bottom row of condenser tubes first.
Check Evaporator Refrigerant Temperature sensor.
Check for division plate gasket bypass.
Check for fouled tubes.
Condenser water too cold or chiller shut down with brine below 0°C in
cooler so equalization temperature in chiller approached 0°C.
Check condenser pressure transducer.
Check refrigerant charge.
Actual VFD Speed on COMPRESS screen must not exceed Target VFD
Speed by more than 10%.
Check 25%, 50%, and 75% Guide Vane and Diffuser Load Point entries
in SETUP2 screen.
Confirm that Diffuser Option in SETUP 2 screen has not been Enabled if
compressor does not have a split ring diffuser. May indicate rotating stall
condition.
Check rotating stall transducer wiring, accuracy and sealing.
Check diffuser schedule and guide vane schedule in SETUP2 screen.
Check for proper operation of diffuser and inlet guide vane actuators
including inlet guide vane calibration.
Check diffuser actuator coupling for rotational slip.
Check RC snubber on CCM J4-23 and J4-24.
Check 4.3 kOhm resistor between CCM terminals J3-7 and J3-8.
Check for electrical noise in CCM Diffuser Pressure wiring. Do not continue
to operate compressor except for diagnostic purposes.
Check Spare Temperature Enable and Spare Temperature Limit in
SETUP1 Screen.
Check component that SPARE TEMPERATURE #2 is Check Spare
Temperature Enable and Spare Temperature Limit in SETUP1 Screen.
The VFD_CONF table in the Gateway does not match that which is in the
ICVC. This is a normal fault if an ICVC has been uploaded with software
when it was not attached to the CCM. Enter VFD_CONF screen and
then exit VFD_CONF screen by pressing EXIT then CANCEL. Re-enter
the VFD_CONF screen, press EXIT then SAVE. Parameters stored in
the Gateway will be uploaded into the ICVC. Confirm valid settings in
VFD_CONF screen.
The VFD_CONF table in the Gateway does not match that which is in
the ICVC.
Enter CONTROL TEST and execute Guide Vane Calibration.
Check CCM guide vane feedback terminals J4-9 and J4-10.
Check guide vane feedback potentiometer. Alarm before start indicates
guide vane opening is not less than 4%. Alarm running indicates guide
vane position is < -1% or > 103%, or feedback voltage is < 0.045 or
> 3.15 V d.c.
Actual VFD checksum does not match calculated value.
VFD COLDPLATE TEMP is too close to dew point based on VFD
ENCLOSURE TEMP and RELA¬TIVE HUMIDITY in POWER screen.
Check for moisture in VFD enclosure.
Check Humidity Sensor in CONTROLS TEST.
Check for contamination on CCM J3-7 and J3-9 Humidity Sensor.
Check that VFD refrigerant cooling modulating valve is closing.
Check for cooling fan air flow obstructions.
The VFD Start Inhibit is derived from the Alarm bit being set in the VFD.
The conditions causing the alarm must be corrected in the VFD to
enable subsequent starts and operation. See VFD parameters 212/214.
CCN has signaled the chiller to stop.This fault must be manually reset
from the default screen of the ICVC.
LINE FREQUENCY in POWER screen must be maintained between 45-
52 Hz if LINE FREQ=60Hz? is set to NO (50 Hz). LINE FREQUENCY
must be maintained between 55-62 Hz if LINE FREQ=60Hz? is set to
YES (60 Hz).
Check 2C AUX/HPR Gate Kill circuit.
COMPRESSOR 100% SPEED in VFD_CONF screen must be set
between 45-52 Hz if LINE FREQ=60Hz? is set to NO (50 Hz).
COMPRESSOR 100% SPEED must be set between
55-62 Hz if LINE FREQ=60Hz? is set to YES (60 Hz).
VFD Gateway and VFD software versions are not compatible.
Call Carrier Service.
VFD Gateway and ICVC software versions are not compatible.
Call Carrier Service.
Check for high entering water temperature or low condenser water flow.
Check current settings in VFD_CONF screen.