Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 60

19xrv pic iii control hermetic centrifugal liquid chillers
Table of Contents

Advertisement

I.
CHILLER PROTECTIVE LIMIT FAULTS
ICVC
PRIMARY MESSAGE
FAULT
STATE
200
PROTECTIVE LIMIT
201
PROTECTIVE LIMIT
202
PROTECTIVE LIMIT
203
FAILURE TO START
204
FAILURE TO STOP
205
PROTECTIVE LIMIT
206
PROTECTIVE LIMIT
207
PROTECTIVE LIMIT
208
PROTECTIVE LIMIT
209
PROTECTIVE LIMIT
210
PROTECTIVE LIMIT
211
PROTECTIVE LIMIT
212
PROTECTIVE LIMIT
213
PROTECTIVE LIMIT
214
PROTECTIVE LIMIT
215
PROTECTIVE LIMIT
216
PROTECTIVE LIMIT
217
PROTECTIVE LIMIT
218
PROTECTIVE LIMIT
219
PROTECTIVE LIMIT
220
PROTECTIVE LIMIT
221
PROTECTIVE LIMIT
222
PROTECTIVE LIMIT
223
LOSS OF
COMMUNICATION
224
PROTECTIVE LIMIT
225
PROTECTIVE LIMIT
226
PROTECTIVE LIMIT
227
PROTECTIVE LIMIT
*
[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., setpoint predefined or selected by the operator as an override, alert, or alarm condition.
[VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
60
Table 10 - Alarm and alert messages (continued)
SECONDARY
PRIMARY CAUSE
MESSAGE
RECTIFIER POWER
200->Rectifier Power Fault: Check VFD
FAULT
Status
INVERTER POWER
201->Inverter Power Fault: Check VFD
FAULT
Status
MOTOR AMPS NOT
202->Motor Amps Not Sensed -
SENSED
Average Load Current [VALUE]
MOTOR
203->Motor Acceleration Fault -
ACCELERATION
Average Load Current [VALUE]
FAULT
VFD SHUTDOWN
204->VFD Shutdown Fault: Check
FAULT
Inverter Power Unit
HIGH DC BUS
205->High DC Bus Voltage: [VALUE]
VOLTAGE
exceeded limit of [LIMIT]*
VFD FAULT
206->VFD Fault Code: [VALUE]; Check
VFD Fault Code List
HIGH CONDENSER
207->High Cond Pressure trip. [VALUE]
PRESSURE
exceeded Switch Trippoint.
EXCESSIVE MOTOR
208->Percent Load Current [VALUE]
AMPS
exceeded limit of [LIMIT]*.
LINE CURRENT
209->Line Current Imbalance: Check
IMBALANCE
VFD Fault History for Values.
LINE VOLTAGE
210->Single Cycle Line Voltage Dropout Temporary loss of voltage. Disable Single Cycle Dropout in VFD_
DROPOUT
HIGH LINE VOLTAGE
211->High Percent Line Voltage
[VALUE]
LOW LINE VOLTAGE
212->Low Percent Line Voltage
[VALUE]
VFD MODULE RESET
213->VFD Module Power-On Reset
When Running
POWER LOSS
214->Control Power Loss When
Running
LOW DC BUS
215->Low DC Bus Voltage: [VALUE]
VOLTAGE
exceeded limit of [LIMIT]*
LINE VOLTAGE
216->Line Voltage Imbalance; Check
IMBALANCE
VFD Fault History for Values.
MOTOR OVERLOAD
217->Motor Overload Trip; Check VFD
TRIP
configurations
VFD RECTIFIER
218->VFD Rectifier Temp Exceeded:
OVERTEMP
Check Cooling and VFD Config.
VFD INVERTER
219->VFD Inverter Temp Exceeded:
OVERTEMP
Check Cooling and VFD Config.
GROUND FAULT
220->Ground Fault Trip; Check Motor
and Current Sensors
UNUSED
UNUSDED
LINE FREQUENCY
222->Line Frequency [VALUE]: exceeded
TRIP
limit of [LIMIT]: Check Power Supply.
WITH VFD GATEWAY
223->Loss of SIO Comm with VFD
MODULE
Gateway: Check VFG Module and
Power
VFD
224->Loss of DPI Comm with VFD
COMMUNICATIONS
Gateway: Check VFG to VFD Comm.
FAULT
MOTOR CURRENT
225->Motor Current Imbalance: Check
IMBALANCE
VFD Fault History for Values.
LINE PHASE
226->Line Phase Reversal: Check Line
REVERSAL
Phases
OIL PRESS SENSOR
227->Oil Pressure Delta P [VALUE]
FAULT
(Pump Off): Check Pump/Transducers
ADDITIONAL CAUSE/REMEDY
Malfunction within VFD Power Module.
Call Carrier Service.
Malfunction within VFD Power Module.
Call Carrier Service.
Check main circuit breaker for trip. Increase Current % Imbalance
in VFD_CONF screen.
Check that inlet guide vanes are fully closed at start-up.
Check Motor Rated Load Amps in VFD_CONF screen. Reduce
unit pressure if possible.
VFD Circuit Board malfunction.
Call Carrier Service.
Verify phase to phase and phase to ground line voltage. Monitor
AC line for high transient voltage conditions. VFD Circuit Board
malfunction. Call Carrier Service.
See VFD Fault Code description and corrective action.
Check Compressor Discharge High Pressure switch wiring and
accuracy.
Check for high condenser water temperatures, low water flow,
fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables in refrigerant.
Check Motor Rated Load Amps in VFD_CONF screen. Percent
Load Current > 110%.
Check Motor Rated Load Amps setting.
Check phase to phase and phase to ground power distribution
bus voltage.
Check Line Current % Imbalance in VFD_CONF screen. Consult
power company.
CONF screen.
Check phase to phase and phase to ground distribution bus
voltage. Consult power company.
Check phase to phase and phase to ground distribution bus
voltage. Consult power company.
Temporary loss of VFD control voltage. Check VFD control
power breaker, transformer and fuses.
Check phase to phase and phase to ground distribution bus voltage.
Check VFD fuses.
Check 24 V a.c. power supply to ICVC.
Consult power company.
Verify phase-to-phase and phase-to-ground line voltage. VFD
Circuit Board malfunction.
Call Carrier Service.
Check phase-to-phase and phase-to-ground distribution bus
voltage. Increase Line Voltage % Imbalance in VFD_CONF screen.
Any phase current > 106% RLA. Can result from significant load
side current imbalance when running at full load.
Check entering condenser water temperature and water flow rate.
Check Motor Rated Load Amps in VFD_CONF screen.
Check that VFD refrigerant isolation valves are open.
Check VFD refrigerant cooling solenoid and refrigerant strainer.
Check for proper VFD cooling fan operation and blockage.
Check that VFD refrigerant isolation valves are open.
Check VFD refrigerant cooling solenoid and refrigerant strainer.
Check for proper VFD cooling fan operation and blockage.
Check for condensation on motor terminals. Check motor power
leads for phase to phase or phase to ground shorts. Disconnect
motor from VFD and megger motor.
Call Carrier Service.
If operating from a generator, check generator size and speed.
Check utility power supply.
Check VFD communication wiring and connectors on VFD
Gateway and DPI board.
Check for compatibility between ICVC and Gateway software.
Check VFD communication wiring and connectors.
Check status lights on DPI Communications Interface Board.
Call Carrier Service.
Check Motor Current % Imbalance in VFD_CONF screen.
Reverse connections of any two line conductors to circuit
breaker.
Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check transducer calibration.