3 About the box

WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
WARNING
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
3
About the box
3.1

Outdoor unit

3.1.1
To remove the accessories from the
outdoor unit
a
b
c
d
a
Outdoor unit installation manual
b
Fluorinated greenhouse gases label
c
Multilingual fluorinated greenhouse gases label
d
Drain plug (located at bottom of packing case)
4

Preparation

4.1

Preparing installation site

▪ Choose the installation location with sufficient place for carrying
the unit in and out of the site.
▪ Choose a location where the hot/cold air discharged from the unit
or the operation noise, will NOT disturb anyone.
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Avoid areas where flammable gas or product might leak.
Installation manual
8
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
3 metre may not be sufficient.
WARNING
Do NOT place objects below the indoor and/or outdoor unit
that may get wet. In this condition, condensation on the
main unit or refrigerant pipes, air filter dirt or drain blockage
may cause dripping. This results in fouling or failure of the
object which is located beneath the unit.
4.1.1
Installation site requirements of the
outdoor unit
Mind the following spacing guidelines:
>100
>350
b
a
(mm)
a
Air outlet
b
Air inlet
NOTICE
▪ Do NOT stack the units on each other.
▪ Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet
causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
Do NOT install the unit in the following places:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
b
>100
a
>50
(mm)
b
a
RXS50+60 + RX50+60 + ARXS50~71
R410A split series
3P360062-1H – 2016.09