Using The Stop Valve And Service Port; To Connect The Refrigerant Piping To The Outdoor Unit - Daikin RXS50K2V1B Installation Manual

R410a split series
Hide thumbs Also See for RXS50K2V1B:
Table of Contents

Advertisement

Flare tool for
R410A (clutch
Clutch type
type)
(Ridgid-type)
A
0~0.5 mm
1.0~1.5 mm
5 Check that the flaring is properly made.
a
b
c
a
Flare's inner surface must be flawless.
b
The pipe end must be evenly flared in a perfect circle.
c
Make sure the flare nut is fitted.
5.3.5

Using the stop valve and service port

To handle the stop valve
Take the following guidelines into account:
▪ The stop valves are factory closed.
▪ The following illustration shows each part required in handling the
valve.
a
b
c
d
a
Service port and service port cap
b
Valve stem
c
Field piping connection
d
Stem cap
▪ Keep both stop valves open during operation.
▪ Do NOT apply excessive force to the valve stem. Doing so may
break the valve body.
▪ Always make sure to secure the stop valve with a spanner, then
loosen or tighten the flare nut with a torque wrench. Do NOT place
the spanner on the stem cap, as this could cause a refrigerant
leak.
a
Spanner
b
Torque wrench
▪ When it is expected that the operating pressure will be low (e.g.
when cooling will be performed while the outside air temperature
is low), sufficiently seal the flare nut in the stop valve on the gas
line with silicon sealant to prevent freezing.
Silicon sealant, make sure there is no gap.
To open/close the stop valve
1 Remove the valve cover.
2 Insert a hexagon wrench (liquid side: 4  mm, gas side: 6  mm)
into the valve stem and turn the valve stem:
RXS50+60 + RX50+60 + ARXS50~71
R410A split series
3P360062-1H – 2016.09
Conventional flare tool
Wing nut type
(Imperial-type)
1.5~2.0 mm
a
b
Counterclockwise to open.
Clockwise to close.
3 When the valve stem cannot be turned any further, stop turning.
The valve is now opened/closed.
To handle the stem cap
Take the following guidelines into account:
▪ The stem cap is sealed where indicated with the arrow. Do NOT
damage it.
▪ After handling the stop valve, make sure to tighten the stem cap
securely.
▪ For the tightening torque, refer to the following table.
▪ Check for refrigerant leaks after tightening the stem cap.
Item
Stem cap, liquid side
Stem cap, gas side
Service port cap
(a)
For class 50 and 60.
(b)
For class 71.
To handle the service cap
Take the following guidelines into account:
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, tighten the service port cap
securely. For the tightening torque, refer to the table in chapter
"To handle the stem cap" on
page 13.
▪ Check for refrigerant leaks after tightening the service port cap.
5.3.6
To connect the refrigerant piping to the
outdoor unit
1 Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.
5 Installation
Tightening torque (N∙m)
(a)
21.6~27.4
(b)
32.7~39.9
(a)
48.1~59.7
(b)
60.1~74.6
10.8~14.7
Installation manual
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents