Connection And Wiring; Cautions On Connection - Mitsubishi FX2N-16LNK-M User Manual

Melsec-i/o link remote i/o system master block
Table of Contents

Advertisement

FX
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
2N
3.

Connection and Wiring

3.1

Cautions on connection

Cautions on design
Construct interlock circuits on a sequence program so that the system operates conservatively
when a communication error has occurred in a data link.
If the system does not operate conservatively, an accident may be caused by erroneous outputs
and/or malfunction.
Never bind control cables and communication cables together with power cables. Never locate
control cables and communication cables near major circuits. Keep the distance of 100 mm or
more.
If sufficient distance is not kept, malfunction may be caused by noises.
Connection and Wiring 3