Mitsubishi FX2N-16LNK-M User Manual page 43

Melsec-i/o link remote i/o system master block
Table of Contents

Advertisement

FX
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
2N
[ Example of I/O assignment in dedicated I/O type unit mode ]
X000 to 007
X010 to
Y000 to 007
027
FX
-16MR
16EX
2N
I/O occupation setting switch
MOD0: ON
32 points are occupied.
MOD1: OFF
MOD2: OFF
Dedicated I/O type unit mode
The table below shows I/O assignment for remote I/O units in the system above.
X30
X
Y
Station
0
1
No.
A
Units B and C are units having 4 points dedicated to output. If a unit having 8 points dedicated to output
is connected as Unit C (station No. 3), latter four points will malfunction.
Station Nos. for input and station Nos. for output are already determined respectively. Even if the number
of occupied I/O points is not more than the specified number, an inappropriate unit cannot be connected.
For example, if a unit having eight points dedicated to input is connected to the station No. 6 or 7 which is
set for output, it will not function at all.
Y010 to
X030 to 047
027
Y030 to 047
Y030 to 033
Master
B
16EYR
4 output points
unit
(1 station)
Station
No.2
X40
Y30
2
3
4
5
B
C
D
X030 to
037
Y034 to 037
C
A
4 output points
8 output points
(1 station)
(2 stations)
Station
Station
No.3
No.0
T branch
Y040 to 047
E
8 output points
(2 stations)
Station
No.6
Y40
: A bold line frame shows one remote unit.
6
7
E
Operation 4
X040 to 047
D
8 output points
(2 stations)
Station
No.4
4-17