-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
2N
4.4

Program

Set the station Nos., set the mode and perform wiring in accordance with "4.1 Operating procedure".
Set the station Nos. and the mode using the following procedure.
Standard mode
1 ) Set the I/O occupation setting switch MOD2 to ON (initial value). I/O No. assignment in the standard
mode is selected.
2 ) By turning on/off the switches MOD0 and MOD1, determine the number of I/O points occupied by the
remote I/O system.
3 ) Assign a station No. and I/O Nos. to each remote I/O unit to be used. (Refer to the assignment table
offered as attachment.)
When 128 points are occupied
X (input)
Y (output)
Station No.
0
1
2
3
4
5
6
7
8
9
A
B
Operation 4
C
D
E
F
4-8