Table 1-1 Function Of Keys - Honeywell DR4500A Product Manual

Classic series circular chart recorder with or without control
Hide thumbs Also See for DR4500A:
Table of Contents

Advertisement

Overview
Operator Interface
Key functions
Table 1-1 shows each key on the operator interface and defines its function.
Key
SET
UP
FUNC
LOWR
DISP
MAN
AUTO
CHART
RUN
HOLD
4
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual

Table 1-1 Function of keys

Places the controller in the Configuration Set Up group select mode. Sequentially
displays Set Up groups and allows the FUNC key to display individual functions in
each Set Up group.
Used in conjunction with the SET UP key to select the individual functions of a
selected Configuration Set Up group.
Used to toggle between SP1 and SP2.
Used during field calibration procedure.
Selects an operating parameter to be shown in the lower display:
OUT
= Output Value
SP
= Local Setpoint 1
SPN
= Current setpoint for setpoint rate applications
2SP
= Local Setpoint 2
RSP
= Remote Setpoint
2IN
= Input 2
DEV
= Deviation
EU
= PV Engineering Units
RH
= % RH Value
PIDSETX = Tuning Parameter Set X=1 or 2
RAMP
= Minutes remaining in Setpoint Ramp
#RA
= Minutes remaining in SP Prog Ramp
#SK
= Minutes remaining in SP Prog Soak
RECYC
= Number of recycles left in SP Program
= Time remaining in Timer function
= Time elapsed in Timer function
TUNExXXX = Accutune II indicator. x = 1 or 2
ATTENTION
The lower display can be configured to scroll through the operating
parameters.
Alternately selects:
AUTO Lower display automatically displays setpoint value in engineering units.
MAN
Lower display automatically indicates output in %.
Used to stop recording operation and move pen to outer limit for chart change.
Alternate action switch initiates or holds the Setpoint Ramp or Setpoint Program.
In configuration mode, restores the original value or selection if you do not want to
enter a change you are making to a parameter.
Increases the setpoint, output, or configuration values displayed.
Used to step through the items in each function while in configuration mode plus
adjust control variables in the lower display.
Decreases the setpoint, output, or configuration values displayed.
Used to step through the items in each function while in configuration mode plus
adjust control variables in the lower display.
Function
Release M
April 2017

Advertisement

Table of Contents
loading

Table of Contents