Servo On Function - Omron 3G3RX User Manual

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

4-3 Functions When PG Option Board (3G3AX-PG01) Is Used
(4) The current position is set to the area corresponding to the position command source set in
teaching selection P074.
(However, the P074 setting is not stored. After the power is shut off or after reset, this parameter
is indicated as "00" (x00).)
P074 set values
4

Servo ON Function

This function brings the Inverter into speed servo lock status via an input terminal when "05" (sensor
vector control) is selected in V/f characteristics selection A044.
Allocate 54 (SON) to the desired multi-function input.
The Inverter does not accept the RUN command unless the SON terminal is turned on when SON
is allocated.
If the SON terminal is turned off during operation, the Inverter goes into free-run status. When the
SON terminal is turned on again, the Inverter restarts according to the setting of free-run stop se-
lection b088.
This function cannot be simultaneously used with the preliminary excitation function (55: FOC). If
FOC and SON are both allocated to multi-function input terminals, priority is given to FOC, and SON
is disabled.
SON
FW(RV)
Output
frequency
Related functions
4-143
Position commands to be set
00
P060: Multi-step position command 0
01
P061: Multi-step position command 1
02
P062: Multi-step position command 2
03
P063: Multi-step position command 3
04
P064: Multi-step position command 4
05
P065: Multi-step position command 5
06
P066: Multi-step position command 6
07
P067: Multi-step position command 7
ON
ON
Speed servo-lock status
ON
ON
Free running
Restarts according to b088.
A044,
C001 to C008
ON
Does not operate
because the SON
terminal is OFF.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents