PRODUCT DESIGN
If the combustion air intake pipe is to be installed above a
finished ceiling or other area where dripping of condensate
will be objectionable, insulation of the combustion air pipe
may be required. Use 1/2" thick closed cell foam insulation
such as Armaflex or Insultube where required.
AMH9, GMH9, AMS95, GMS95
Dire ct Ve nt (Dual Pipe )
Maximum Allow able Length of Vent/Flue & Combustion
Air Intake Pipe (f t)
Pipe
Unit Input
Vent/Flue/Air Intake
Size
(Btu)
Termination
(in.)
Standard
2
045_3
Alternate
2
Standard
2
070_3
Alternate
2
Standard
2
070_4
Alternate
2
Standard
3
090_4
Alternate
3
Standard
3
090_5
Alternate
3
Standard
3
115_5
Alternate
3
1) Minimum requirement for each vent pipe is five (5) feet in length and
one elbow/tee.
2) Tees and/or elbows used in the vent/flue termination must be in-
cluded when determining the number of elbows in the piping sys-
tem.
3) 3" diameter pipe can be used in place of 2" diameter pipe.
4) Increased Clearance Configurations using (2) 45 deg. Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
Direct Vent (Dual Pipe)
Maximum Allowable Length of Vent/Flue & Combustion
Air Intake Pipe (ft)
Unit Input
Vent/Flue/Air Intake
(Btu)
Termination
Standard
045_3
Alternate
Standard
Alternate
070_3
Standard
Alternate
Standard
070_4
Alternate
Standard
Alternate
090_4
Standard
Alternate
Standard
Alternate
090_5
Standard
Alternate
Standard
115_5
Alternate
48
(1)(2)(3)(5)
Number of Elbow s
(4)
2
3
4
5
6
68
65
62
59
56
55
52
49
46
43
68
65
62
59
56
55
52
49
46
43
40
46
43
Not Recommended
33
30
27
68
65
62
59
56
55
52
49
46
43
68
65
62
59
56
55
52
49
46
43
68
65
62
59
56
55
52
49
46
43
GKS9
Pipe
Number of Elbows
(4)
Size
(in.)
2
3
4
5
6
2
68 65 62 59 56 53 50
2
55 52 49 46 43 40 37
2
36 33 30 27 24 21 18
2
23 20 17 14 11 8
3
68 65 62 59 56 53 50
3
55 52 49 46 43 40 37
2
55 52 49 46 43 40 37
2
42 39 36 33 30 27 24
2
37 34 31 28 25 22 19
2
24 21 18 15 12 9
3
68 65 62 59 56 53 50
3
55 52 49 46 43 40 37
2
39 36 33 30 27 24 21
2
26 23 20 17 14 11 8
3
68 65 62 59 56 53 50
3
55 52 49 46 43 40 37
3
68 65 62 59 56 53 50
3
55 52 49 46 43 40 37
1) Elbows and/or tees used in terminations must be included when
determining quantity of allowable elbows in the system.
2) Number of elbows tabulated are for each (Vent/Flue & Combustion
Air Intake) pipe.
3) Minimum requirements for each Vent/Flue & Combustion Air Intake
pipe is five (5) feet in length and one elbow/tee.
4) 3" diameter pipe can be used in place of 2" diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
ACV9, AMV9, GCV9, GMV9, GMV95
7
8
53
50
Direct Vent (Dual Pipe) Maximum Allow able Length
40
37
of Vent/Flue & Combustion Air Intake Pipe (ft)
53
50
Unit Input
Termination
40
37
(Btu)
Style
Standard
53
50
45,000
Alternate
40
37
53
50
Standard
40
37
70,000
53
50
40
37
Alternate
Standard
90,000
Alternate
Standard
115,000
Alternate
Direct Vent (Dual Pipe) Maximum Allow able Length
of Vent/Flue & Combustion Air Intake Pipe (ft)
Unit Input
Termination
(Btu)
Style
Standard
70,000
Alternate
(1)(2)(3)(5)
Standard
7
8
90,000
Alternate
1) Elbows and/or tees used in terminations must be included when
5
determining quantity of allowable elbows in the system.
2) Number of elbows tabulated are for each (Vent/Flue & Combustion
Air Intake) pipe.
3) Minimum requirements for each Vent/Flue & Combustion Air Intake
pipe is five (5) feet in length and one elbow/tee.
4) 3" diameter pipe can be used in place of 2" diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
6
Vent/Flue and Combustion Air Pipe Terminations
V
/F
ENT
LUE AND
The vent/flue and combustion air pipes may terminate verti-
cally, as through a roof, or horizontally, as through an out-
side wall.
UPFLOW
Number of Elbow s
Pipe
(4)
(inch)
1
2
3
4
2
71
68
65
62
2
58
55
52
49
2
49
46
43
40
3
71
68
65
62
2
36
33
30
27
3
57
54
51
48
3
71
68
65
62
3
57
54
51
48
3
49
46
43
40
3
35
32
29
26
COUNTERFLOW
Number of Elbow s
Pipe
(4)
(inch)
1
2
3
4
2
49
46
43
40
3
71
68
65
62
2
36
33
30
27
3
57
54
51
48
2
61
58
55
52
3
71
68
65
62
2
48
45
42
39
3
57
54
51
48
C
A
P
T
OMBUSTION
IR
IPE
ERMINATIONS
(1)(2)(3)(5)
5
6
7
8
59
56
53
50
46
43
40
37
37
34
31
28
59
56
53
50
24
21
18
15
45
42
39
36
59
56
53
50
45
42
39
36
37
34
31
28
23
20
17
14
(1)(2)(3)(5)
5
6
7
8
37
34
31
28
59
56
53
50
24
21
18
15
45
42
39
36
49
46
43
40
59
56
53
50
36
33
30
27
45
42
39
36